Laserfiche WebLink
Test No. : 900523 <br /> Test Date May 23, 1990 <br /> Location U. S. Sprint <br /> 3207 Coronado Avenue <br /> Stockton, CA <br /> TEST RESULTS <br /> WATER HIGH LEVEL LOW LEVEL <br /> PRODUCT VOLUME IN TANK LEAK RATE LEAK RATE FULL TANK <br /> (GAL) (INCHES) (GPH) (GPH) SYSTEM ONLY <br /> waarewaawme®awsmaravacasaoamrrim rwwmmmwwicc0ouam®arwrrrwaraerrrwr arwrwarrawww <br /> FUEL OIL 6,000 o.00 0.00 @ 28" - PASS PASS <br /> x <br /> LEAK HEIGHT ANALYSIS <br /> The high level test of the FUEL OIL tank system is <br /> considered sufficient for certification purposes since <br /> the water level in the backfill area is below the point <br /> of hydrostatic equilibrium. <br /> SUCTION PRODUCT LINE TEST RESULTS <br /> �'����r++31E�RT«SC 7A rla amsaw:arsr:rrwramr <br /> Tight to a level of 28" above tank top. <br />