Laserfiche WebLink
6. Overfill Protection System (spill catchment basins required) <br /> A. Nonmotor vehicle fuels (See Option IA) <br /> 1 . Level sensing device and #2 or #3 below L ' - D P <br /> 2. Audible/visual alarm triggered to liquid level sensor 3 <br /> 3. Automatic shut-off device 0 P40 - (,,/ _'4 p,- - --- <br /> B. Motor vehicle fuels only <br /> 1 ,. Manual monitoring <br /> a. Written filling procedure provided <br /> b. Procedure addresses all of the following: <br /> 1 ) Visual monitoring of fuel level and filling operation <br /> 2) Available caacity of tank is at 103% or +200 gallons <br /> (2635- 9) (AM)(C)) <br /> 3) Metered input �}I <br /> C. Spill catchment basin size <br /> 1 . Minimum 5 gallons <br /> 10. Secondary containers (Includes leak interception and detection systems) . <br /> A. Backfill in secondary container -(_ Article 3, Section 2635) <br /> 1 . See Article 3 Section 2635(c) (1-8) . <br /> B. Two or+ more primary containers within secondary container (Demonstrate <br /> product compatibilities). <br /> C. Liquids detected in secondary containment must be sampled and analyzed for <br /> hazardous substances. (Article 3, Section 2635(6) and Health and Safety <br /> Code 25291 (e)(h) . <br /> D. Water tight cover for secondary container excavation (Article 3, Section <br /> 2635(7)) . <br /> ll . Piping / <br /> A. Double containment required for: �`d' ur, uJ - / <br /> 1 . Product and vapor recovery lines. <br /> 2. Vent line excluded only if ball float valve is installed) . <br /> lezZ <br /> rr�rr , <br /> a-4 f--,i-o cam' Y 0 PGG) & 5_ 3 p I" <br />