Laserfiche WebLink
Integrity Tank Testing Systems, Inc. <br /> ,• i47 <br /> , N <br /> � s <br /> 3 <br /> May 20, 1992 <br /> N t <br /> , <br /> I N <br /> Mr. Ren Belcher J\ ` <br /> San Joaquin County Solid Waste ` r <br /> P. O. Box 1810 <br /> 7 m <br /> Stockton California 95201 <br /> Site: 31130 Corral Hollow Rd <br /> Tracy, Ca. <br /> Dear Mr. Belcher; <br /> Following is a summary of the precision testing we recently <br /> conducted on the underground storage tank at the above <br /> site. <br /> Enclosed are copies of the test worksheets, graphs, and/or <br /> computer summation for your submittal to the appropriate <br /> governmental agency. Individual computer generated readings <br /> will be forwarded as requested. <br /> A tank system may be considered tight, according to the <br /> current regulations if the the test results shown below do <br /> not exceed 0 .05 gph. If the results are beyond this <br /> parameter, an unauthorized release may have occurred, and <br /> you should consider taking remedial action. <br /> TANK # OR TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> West 1,659 Diesel Fuel -.023 Yes <br /> Please contact us if you need additional information or <br /> data. I I o <br /> Sincerely, z �I roi ItiI I ° i <br /> IO <br /> W. N. Savage; i <br /> Certified Tef <br /> I j iLi <br /> s <br /> 800 262-8378 16 95206 (209) 3d <br />