5 t • • <br /> LDT 5000 Field Test Apparatus Page 1 of 1 <br /> Tanknology Line Leak Detector Test <br /> Work Order: 2302041 Date: 2/17/2012 <br /> Site Name / ID: 7-ELEVEN #14117 MKT 2368 / 14117 <br /> Address: 2725 COUNTRY CLUB BLVD <br /> City: STOCKTON State: CA Zip: 95204 <br /> Tank ID 2 <br /> Product UNLEADED PREMIUM <br /> Product Line 1 1 <br /> Tested From 1 1 <br /> Existing/New Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-200 Vaporless LD-200 <br /> Serial No. 04011556 ----1983 <br /> Pump Operating Pressure(psi) 30.00 30.00 <br /> Calibrated Leak(mllmin) 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 <br /> Holding PSI 30.00 30.00 <br /> 'NIA for Electronic LID'S <br /> Resiliency(ml) 50.00 100.00 <br /> 'NIA for Electronic LD's <br /> Metering PSl 23 ig <br /> •N/A for Electronic Lo's <br /> Opening Time(see) 5 5 <br /> -N/A for Electronic Lo's <br /> Test Results Pass Pass <br /> Technician Comments: <br /> Technician Name: Jarrod Cooke Certification#: 1352 <br /> Technician Signature: U <br /> Environmental Compliance for Petroleum Systems <br /> *M10TanknobVlz.,Au9n.Tx. alrghNn,e Sd. unknoogy.. <br />