Laserfiche WebLink
TANKNOLOGY UNDEF..9ROU1v"'D LEAK DETECTION SYSTEM - . 1 Pane 18 <br /> SHELL HOL19203-IVE910623-46739-03 May 11, 1992, 05:45 <br /> S3 i J 1"l M+L'4 F-.! Y <br /> TEST DATE ; Mar 11 , 1992 <br /> START TIME : 05: 45: 00 <br /> CLIENT ; SHELL <br /> LOCATION NAME : SHELL <br /> L.00:ATION CODE : 7524-0402 <br /> TANK: CONFIGURATION : Single <br /> TANK CONTENTS : S/R/UNL <br /> TANK NUMBER : 03 <br /> TANK DIAMETER , 94 in <br /> TANK CAPACITY : 6000 13 <br /> TANK MANUFACTURER! <br /> TANK MATERIAL. Steel <br /> TANK. REGISTRATION # <br /> TANK. DATE INSTALLED / <br /> INITIAL. DIPPED FUEL LEVEL ; 61 . 00 in <br /> INITIAL DIPPED WATER LEVET_ ; 0. 00 in <br /> POST PUMPING; WATER LEVEL 0. 00 in <br /> T"A P4 k=:: -T'I=—S3 T" 1=='E_:E3 ILJ L.-F <br /> TEST INITIAL WATER LEVEL , 0. 00 in <br /> TEST FINAL WATER LEVEL : 0. 00 in <br /> WATER INGRESS : 0. 00 in <br /> BUBBLE SIGNATURES : No <br /> VACU--TEC:T TEST RESULT ; Passed <br /> COMMENTS: <br /> CONCLUSION: S/R/UNLEADED TANK: TESTED TIGHT. <br /> i <br /> L.- I rA E -T"1=-S3-1- F;-t E.S LJ L."T" <br /> TEST RATE <br /> 1 <br /> LINE _ RESULT _ PRESSURE OF LOSS <br /> #1 Passed TO PSI 0. 00 GPH <br /> #2 <br /> #.^- <br /> #4 <br /> #5 <br /> #6 <br /> i <br /> COMMENTS: <br /> i <br /> CONCLUSION: S/R/UNL LINE TESTED TIGHT. <br /> I ; <br /> This test was conducted in accordance with O.S. EPA Rule 40 CFR Parts 280 and 281. <br /> _ _ -----__-..---- HOU9203-IVE.910623--40/39-03 <br /> KEN BROWN VAC:U-TECT(tm) Test Number <br />