Laserfiche WebLink
INDIVIDUA ANK/LINE/LEAK DETECTOR TE REPORT <br /> TEST DATE: 03/10/98 WORK ORDER NUMBER: 2203787 <br /> CLIENT: SHELL OIL COMPANY SITE: SHELL 204-7524-0402 <br /> Tank ID: 1 Material:STEEL Bottom to top fill in inches: 149.5 <br /> Product:PREMIUM Tank manifolded:No Bottom to grade fill in inches: 155.0 <br /> Capacity in gallons: 7,426 Vent manifolded:No Fill pipe length in inches: 54.5 <br /> Diameter in inches: 95.00 Vapor recovery manifolded:YES Fill pipe diameter in inches: 4.0 <br /> Length in inches: 245 Impact Valves Operational: Y Stage I vapor recovery: DUAL <br /> Tank age (years): Overfill protection: NO Stage II vapor recovery: BALANCE <br /> Fuel pure rating: Overspill protection: No Installed: ATG <br /> COMMENTS CP installed on: <br /> ,ttEI <br /> 7 tart m n m Newlpassed Failedlreplaced Newlpassed Falledlreplaced <br /> Dipped Water Level: L.D.#1 L.D.#1 L.D.#2 L.D.#2 <br /> Dipped Product Level: Make:vApoRLEss <br /> Probe Water Level: Model: LD2000 <br /> Ingress Detected: water Bubble Ullage S/N: 32300 <br /> Test time: Open time in sec: 3.00 <br /> VacuTect Test Type: Holding psi: is <br /> VacuTect Probe Entry Point: Resiliancy cc: 160 <br /> Pressure Set Point: Test leak rate ml/m: 189.0 <br /> Tank water level in inches: Metering psi: 10 <br /> Water table depth in inches: Caiib. leak in gph: 3.00 <br /> Determined by (method): Results: PASS <br /> Result: <br /> COMMENTS COMMENTS <br /> Material: SW FIBERG <br /> Diameter(in): 2.0 <br /> Length (ft): 100.0 <br /> Test psi: 50 <br /> Bleedback cc: 8o <br /> Test time (min): 30 <br /> Test 1: Start time: 11:23 <br /> Finish psi: 50 <br /> Vol change cc: a <br /> Test 2:Start time: 11:33 <br /> Finish psi: 50 <br /> Vol change cc: 2 <br /> Test 3: Start time: 11:43 <br /> Finish psi: 50 <br /> Vol change cc: 0 <br /> Final gph: 0.005 <br /> Result: PASS <br /> Pump type: PRESSURE <br /> COMMENTS Pump make: RED JACKET <br /> 8900 SHOAL CREEK, BUILDING 200,AUSTIN,TEXAS 78757(512)451-6334 Draft 03/11198 14:46 MSHAW <br />