Laserfiche WebLink
STOCKTON SERVICE STATION EQUIPMENT CO. INC. <br /> 808 N. UNION STREET 14/1STOCKT <br /> 0 , <br /> PHONE 209.464.8333F 5205-4152 �� <br /> FAX 209.464.8349 q1' <br /> LDT-890 LEAK DETECTOR TEST RECORD ��GFs91�ti <br /> CUSTOMER: Rancho San Miguel Market DATE: June 21,2007 <br /> LOCATION: 1427 S. Airport Way <br /> CITY: Stockton STATE: CA ZIP: 95206 <br /> TECHNICIAN: Eric Molgaard <br /> Submersible Pump Identification <br /> Manufacturer Model Serial Number <br /> Fe Petro <br /> Leak Detector Identification <br /> Manufacturer Description Other Style Leak Detector <br /> Fe Petro <br /> Diaphragm-Type <br /> Piston-type X <br /> Leak Detector in Submersible Pump <br /> Test at Dispenser <br /> 1. Operating Pump Pressure 26 psi (Purging Test System) <br /> 2. Gallons per hour rate 3 Gallon (Leak Test,Phase 1) <br /> 3. Line pressure with pump shut off 12 psi (Leak Test Phase 1) <br /> 4. Bleed-Back Test with pump off 300 ml (Bleed-back Test) <br /> 5. Step-through time to full Bow 8 seconds (Step-through Time) <br /> 6. Leak detector stays in leak search position. (Leak Test Phase I1)Yes X No <br /> LEAK DETECTOR TEST <br /> Note: Pass=Leak detector fits test protocol <br /> Fall =Leak detector fails test protocol <br /> Pass X <br /> Fail <br /> Form 890C <br />