Laserfiche WebLink
San Joaquin County <br /> Environmental Health Department <br /> 1868 East Hazelton Avenue, Stockton, California 95205-6232 <br /> Telephone:(209)468-3420 Fax:(209)468-3433 Web:www.sigov.org/ehd <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> A G SPANOS AVIATION DEPT* 4800 S AIRPORT WAY STOCKTON February22 2016 <br /> On Site Records <br /> 201 CCR 2712(b) Failed to maintain alarm logs and/or records of follow up actions �V o R �COS <br /> 202 CCR 2712(b) Failed to maintain cathodic protection test records on site for at least 6 1/2 years ❑V ❑R ❑COS <br /> 203 CCR 2712(b) Failed to maintain records of monitoring,repair,lining,and upgrades on site ❑V ❑R ❑COS <br /> 204 CCR 2712(i) Current monitoring plan approved by the EHD not found on site ■V ❑R ❑COS <br /> 205 CCR 2712(i) Operating permit not on site ■V c R ❑COS <br /> 206 HSC 25294,25295 Failed to record or report unauthorized release in appropriate time frame ❑V ❑R ❑COS <br /> 207 CCR 2715 Designated operator did not inspect all required items and/or the inspection reports not completed ❑V ❑R ❑COS <br /> 208 CCR 2715 Designated operator monthly inspection reports not maintained on site for at least 12 months ❑V ❑R ❑COS <br /> 209 CCR 2715(f) Designated operator employee training not performed or log not kept ❑V ❑R ❑COS <br /> 210 CCR 2715(f)(2) Unstaffed facility failed to have or implement a training program approved by the EHD ❑V ❑R ❑COS <br /> 211 HSC 25281.5(b)(2) Unburied fuel piping at marinas not visually inspected at least daily or log not kept c V ❑R ❑COS <br /> 212 HSC 25281.5(b)(3) Unburied emergency generator fuel piping not visually inspected at least monthly or log kept ❑V ❑R ❑COS <br /> `UST System Observations <br /> 301 HSC 25292.1 UST system is not operated to prevent unauthorized release,including spills and overfills ❑V ❑R ❑COS <br /> 302 HSC 25291(b) UST system incapable of detecting leak from primary into secondary containment(pre-Jul 2003) ❑V ❑R ❑COS <br /> 303 HSC 25290.2(d) Monitoring system not maintained to detect entry into secondary containment(Jul 2003-Jun 2004) ❑V ❑R ❑COS <br /> 304 HSC 25290.1(d) Monitoring system not maintained to detect entry into secondary containment(after Jul 2004) ❑V ❑R ❑COS <br /> 305 HSC 25290.1(e) VPH monitoring of the interstitial spaces of the UST system is not maintained ❑V ❑R ❑COS <br /> 306 CCR 2630(d) Monitoring equipment is not installed or maintained to detect a leak at the earliest opportunity c V c R ❑COS <br /> 307 CCR 2632(c) Monitoring system of the interstitial space of a double walled system not maintained ❑V ❑R ❑COS <br /> 308 CCR 2636(f) Failed to maintain a continuous monitoring system that activates an audible and visual alarm ❑V ❑R c COS <br /> 309 CCR 2636(f)(1) Monitoring in the UDCs failed to activate an audible and visual alarm or stop the flow at the UDC c V o R ❑COS <br /> 310 CCR 2636(f)(1) Sensor in a turbine sump failed to activate an audible and visual alarm or stop the flow product ❑V ❑R ❑COS <br /> 311 CCR 2635(f)(5) Piping is not fail-safe outside UDCs or fails to stop flow of product at dispenser inside UDCs ❑V ❑R ❑COS <br /> 312 CCR 2636 Failed to properly program or operate leak detection equipment ❑V c R ❑COS <br /> 313 CCR 2638(f) Failed to affix a tag sticker on monitoring equipment certified,repaired,or replaced ❑V ❑R ❑COS <br /> 314 CCR 2631(a) Primary containment not tight(pre-Jul 2003) ❑V ❑R ❑COS <br /> 315 HSC 25290.2(c)(1) Primary containment not tight(Jul 2003Jun2004) ❑V c R ❑COS <br /> 316 HSC 25290.1(c)(1) Primary containment not tight(after Jun 2004) ❑V c R ❑COS <br /> 317 HSC 25290.1,25290.2, Secondary containment not tight ❑V c R ❑COS <br /> 25291 <br /> 318 CCR 2636(a) Failed to have secondary containment ❑V ❑R ❑COS <br /> 319 HSC 25291(a) Water in secondary containment not removed,analyzed,and properly disposed of(pre-Jul 2003) ❑V ❑R ❑COS <br /> 320 HSC 26290.1(c3), Secondary containment not constructed to prevent water intrusion ❑V ❑R ❑COS <br /> 25290.2(c3) <br /> Page 2 of 5 <br />