San Joaquin County <br /> Environmental Health Department <br /> 1868 East Hazelton Avenue, Stockton, California 95205-6232 <br /> Telephone:(209)468-3420 Fax:(209)468-3433 Web:www.si4ov.o[glehd <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> A G SPANOS AVIATION DEPT' 4800 S AIRPORT WAY, STOCKTON February 23, 2018 <br /> UST System Observations <br /> 321 CCR 2635(b)(2) Overfill prevention was overridden c=V o R o COS <br /> 322 HSC 25281.6(x) Unburied below grade emergency generator system failed to meet exemption status ❑V o R o COS <br /> 323 HSC 25283.5(a) Unburied below grade UST system failed to meet exemption status o V ❑R c COS <br /> 324 CCR 2717.1(8) Tampered with red tag o V o R ❑COS <br /> 325 CCR 2717.1(f) Deposited petroleum into a red tagged UST ❑V o R o COS <br /> 326 HSG 25299(a)(9) Tampered with or disabled leak detection devices or alarms ❑V ❑R o COS <br /> 327 CCR 2631.1 UST system not compatible with the substance stored o V ❑R c COS <br /> 328 NSC 25298 Failed to comply with temporary closure requirements o V ❑R o COS <br /> 329 HSC 25298 Failed to comply with all permanent closure requirements o V o R ❑COS <br /> 330 CCR 2636(f)(6) Failure to meet all requirements in lieu of a line leak detector for emergency generator tank system o V o R o COS <br /> 331 CCR 2630(d) Secondarily contained piping not maintained to allow liquid to drain into sump fl V o R o COS <br /> 332 CCR 2631(b),2631(4) Primary and/or secondary containment not constructed in accordance with the established standards ❑V ❑R n COS <br /> Single-Walled Non-Pressurized Piping <br /> 401 CCR 2636(a)(3) Suction piping not properly sloped or incerrectiy located check valve o V ❑R ❑COS <br /> 402 CCR 2643(d) Daily monitoring of suction pipe(pro-Jan 1984)not performed o V o R ❑COS <br /> 403 CCR 2643(d) Triennial 0.1 gph line test for conventional suction piping not performed(pre-January 1984) o V o R o COS <br /> 404 CCR 2643(e) Biennial 0.1 gph test for gravity piping not performed(pre-January 1984) ❑V o R o COS <br /> Other Violations <br /> 2010 See below Unlisted General violation o V ❑R ©COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS Il,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 302 HSC 25291(b) UST system incapable of detecting leak from primary into secondary containment(pre-Jul 2003). <br /> The service technician was unable to get the L1 Tank Annular(Tank 1)and L7 T3 Annular(Tank 3)sensors out of <br /> alarm and the panel back into"All Functions Normal"at the time of inspection and, therefore, tanks 1 and 3 are not <br /> monitored. Both of these sensors were tested and passed at the time of inspection. However,the service technician <br /> indicated that both sensors need to be replaced, but he did not have new sensors to replace the old sensors. <br /> Immediately contact a properly licensed,trained, and certified contractor to replace the failed component with a <br /> functional component immediately.Thomas Tilley was notified that a permit to replace the sensors is not needed as <br /> long as they are replaced'like for like,"however a 48-hour advance notification prior to the work being completed <br /> and a scope of work is required to be submitted to the EHD. <br /> This is a minor violation. <br /> Overall Inspection Comments: <br /> An inspection report was provided to the facility operator on the day of inspection. The report was amended by <br /> the EHD.Violation 302 was added to the report. The amended report replaces the initial report. <br /> Note: At the time of inspection, it was noted that there were one to two L10 Piping Sump S-E Sensor Out <br /> FA0003809 PR0231509 SC001 02/2312018 <br /> EHD 23-01 Rev.091221/6 Page 3 of 4 Underground Storage Tank Program OIR <br />