Laserfiche WebLink
LEAK-TEST METHOD - - - - <br /> TEST ON DATE ALL TANK <br /> JAN 1 , 1996 <br /> START TIME : DISABLED <br /> TEST RATE :0.20 GAL/HR <br /> DURATION : 2 HOURS <br /> OUTPUT RELAY SETUP <br /> LEAI; TEST REPORT FORMAT <br /> NORMAL R 1 :JET FUEL EAST 2 <br /> TYPE: <br /> STANDARD <br /> NORMALLY CLOSED <br /> T 3:JET FUEL EAST 2 <br /> PRODUCT CODE 1 I11-TANK ALARMS <br /> THERMAL COEFF : .000470 T 3:LOW PRODUCT ALARM <br /> TANK DIAMETER 92.00 <br /> TANK PROFILE 4 PTS LIQUID SENSOR ALMS <br /> FULL VOL 11627 i L p:FUEL ALARM <br /> 69.0 INCH VOL 9430 L10:FUEL ALARM <br /> 46.0 INCH VOL 5814 LIQUID SENSOR SETUP L B:SENSOR OUT ALARM <br /> 23.0 INCH VOL 2190 - -- - - - - - - - - - - LID:SENSOR OUT ALARM <br /> L B:SHORT ALARM <br /> L I :TANK I ANNULAR L10:SHORT ALARM <br /> FLOAT SIZE: 4.0 IN. 8496 TRI-STATE (SINGLE FLOAT) <br /> CATEGORY : ANNULAR SPACE R 2:JET FUEL TANK 2 <br /> WATER WARNING 2.0 TYPE: <br /> HIGH WATER LIMIT: 3.0 STANDARD <br /> NORMALLY CLOSED <br /> MAX OR LABEL VOL: 11627 L 2:TANK 1 PROBE SUMP <br /> OVERFILL LIMIT 90. TRP-STATE (SINGLE FLOAT) <br /> 10464 CATEGORY : PIPING SUMP IN-TANK ALARMS <br /> HIGH PRODUCT 95% T 2:LOW PRODUCT ALARM <br /> 11045 <br /> DELIVERY LIMIT 9% L 3:TANK 1 TURBINE SUMP LIQUID SENSOR ALMS <br /> 1046 TRI-STATE (SINGLE FLOAT) L 5:FUEL ALARM <br /> CATEGORY : STP SUMP L 6:FUEL ALARM <br /> LOW PRODUCT 1000 L 9:FUEL ALARM <br /> LEAK ALARM LIMIT: 99 Lll :FUEL ALARM <br /> SUDDEN LOSS LIMIT: 99 L 4:TANK 2 ANNULAR L 5:SENSOR OUT ALARM <br /> TANK TILT 0.00 TRI-STATE (SINGLE FLOAT) L 6:SENSOR OUT ALARM <br /> CATEGORY : ANNULAR SPACE L 9:SENSOR OUT ALARM <br /> MANIFOLDED TANKS Lll :SENSOR OUT ALARM <br /> T#: NONE L 5:SHORT ALARM <br /> L 6:SHORT ALARM <br /> L 5:TANK 2 ANNULAR SUMP L 9:SHORT ALARM <br /> LEAK. MIN PERIODIC: 0f TRI-STATE (SINGLE FLOAT) L1l :SHORT ALARM <br /> 0 CATEGORY : ANNULAR SPACE <br /> R 3:JET FUEL TANK 1 <br /> LEAK MIN ANNUAL 0� TYPE: <br /> STANDARD <br /> L 6:TANK 2 TURBINE SUMP NORMALLY CLOSED <br /> TRI-STATE (SINGLE FLOATS <br /> PERIODIC TEST TYPE CATEGORY : STP SUMP <br /> STANDARD IN-TANK ALARMS <br /> T 1 :LOW PRODUCT ALARM <br /> ANNUAL TEST FAIL L 7:TANK 3 ANNULAR. <br /> ALARM DISABLED TRI-STATE (SINGLE FLOAT) LIQUID SENSOR ALMS <br /> CATEGORY : ANNULAR SPACE L 2:FUEL ALARM <br /> PERIODIC TEST FAIL L 3:FUEL ALARM <br /> ALARM DISABLED L 9:FUEL ALARM <br /> L11 :FUEL ALARM <br /> GROSS TEST FAIL L 8:TANK 3 TURBINE SUMP L 2:SENSOR OUT ALARM <br /> ALARM DISABLED TRI-STATE (SINGLE FLOAT) L 3:SENSOR OUT ALARM <br /> CATEGORY : STP SUMP L 9:SENSOR OUT ALARM <br /> ANN TEST AVERAGING: OFF L11 :SENSOR OUT ALARM <br /> PER TEST AVERAGING: OFF L 2:SHORT ALARM <br /> L 9:PIPING SUMP S-W L 3:SHORT ALARM <br /> TANK TEST NOTIFY: OFF TRI-STATE (SINGLE FLOAT) L 9:SHORT ALARM <br /> CATEGORY : PIPING SUMP L11 :SHORT ALARM <br /> TNK TST SIPHON BREAK:OFF <br /> R 4:UNLOADI NG PUMP <br /> DELIVERY DELAY 1 MIN L10:PIPING SUMP S-E TYPE: <br /> TRI-STATE (SINGLE FLOAT) STANDARD <br /> CATEGORY : PIPING SUMP NORMALLY CLOSED <br /> L11 :PIPING SUMP N-W <br /> TRI-STATE (SINGLE FLOAT) <br /> CATEGORY : PIPING SUMP <br />