Laserfiche WebLink
Oct CZ 08 11:40a Reliable Petroleum 209-845-8953 P.16 <br /> Installation Guide Test of the Leak-Detector <br /> rool If flow is restricted to'abou't 3 gpm (11 Ipm) or less with the nozzle open, the.leak <br /> detector has not:oP.en6d.3Repeat;Step Ba with 'increased running time of:pump to <br /> insure the purging of all air.All air must be purged from the system or the leak detector <br /> will restrict flow to about.;%gpm,, <br /> 91. Affix the enclosed decals to the dispenser dial glass on grade of gasoline upoh�,Which the leak detector is <br /> being installed. Additional decals are available; call customer service'at 1-806473.3313 and request P/N <br /> 046-200-1. <br /> 10. Inspect ail threaded joints to assure they are tight and not leaking. <br /> Test of the Leak Detector <br /> U.S. Environmental Protection Agency (EPA) regulations require annual verification of operation of leak <br /> detector.To assure maintenance of leak detection capability. Red Jacket requires that operation of the <br /> mechanical leak detector be verified by testing upon start-up and that testing cf the leak detector be <br /> performed routinely, at least annually. <br /> L'ad Test procedure options for mechanical leak detectors are explained in Red Jacket <br /> Engineering Reports, RJ20 and RJ21. The Red Jacket Snap Tap Connectors allow the <br /> FX2WFX2DV leak detector to be tested with the FXV Snap Tap Tester as an option to <br /> the above test methods. See Red Jacket literature #042-11 1-1 for test instructions <br /> using Snap Tap Connectors. <br /> 11. The top cover on the Red Jacket leak detector is designed to accommodate a seating wire which can be <br /> used to discourage tampering of the unauthorized removal of leak detector, (see Figure 4). <br /> r'91 I[HA If the dispensing system (the solenoid valve and the nozzle) is opened previous to the <br /> completion of the line test, the FXV Series will detect this opening as a leak and <br /> restricted flow will result. Closing of the nozzle(s) for a period of time adequate to allow <br /> completion of the line test will allow the leak detector to open.Once opened, full pump <br /> flow can be provided. <br /> FX2V;rFX2DV,_*( '_ <br /> Tethered cap <br /> Sealing wire <br /> Snap Tap (provided by <br /> 45'elLow cortractDr) <br /> -inch <br /> T-fitting <br /> SIDE VIEW L TOP VIEW <br /> Vent tube <br /> Figure 4- Installing FXV in the Standard pump <br />