Laserfiche WebLink
ENVIRONMENTAL HEALTH DEPARTMENT <br /> SAN JOAQUIN COUNTY Unit Supervisors <br /> Donna K.Heran,R.E.H.S. Carl Borgman,R.E.H.S. <br /> 304 East Weber Avenue, Third Floor <br /> Director Mike Huggins,R.E.H.S.,R.D.I. <br /> Al Olsen,R.E.H.S. Stockton, California 95202-2708 Douglas W.Wilson,R.E.H.S. <br /> 3. Program ManagerTele -3420 Margaret Lagorio,R.E.H.S. <br /> Laurie A.Cotulls,R.E.H.S, phone: (209) 468 Robert McClellon,R.E.H.S. <br /> Program Manager Fax: (209) 464-0138 Mark Barcellos,R.E.H.S. <br /> March 4, 2003 <br /> Stockton Service Station Equipment Co. Inc. <br /> 808 N. Union Street <br /> Stockton, CA 95205 <br /> Re: 4800 S. Airport Way, Stockton CA <br /> The permit application to repair the annular space riser on the underground storage tank <br /> system from the above referenced facility has been approved with the following <br /> conditions: <br /> 1. The repairs must follow the manufacturers instructions for the underground <br /> storage tank. <br /> 2. EHD must witness a test on the annular space that holds vacuum/pressure for 30 <br /> Minutes. <br /> 3. Submit a complete description of the work performed. <br /> 4. Any further repairs to the system must be approved through EHD and must be <br /> amended to this approved permit. <br /> 5. After concrete is poured, a third party tank integrity test must be performed and <br /> the results sent to EHD <br /> 6. Submit a copy of the secondary containment retest results to EHD within 30 days. <br /> Schedule all appointments 48 hours in advance. <br /> This permit expires on 6/4/03. <br /> If you have any questions please contact me at (209) 468-9848. <br /> Thank you, <br /> Ray von Fliie, R.E.H.S. <br /> Registered Environmental Health Specialist <br />