Laserfiche WebLink
REPORT,. f "SOILTEST" PRECISION TANaTEST ((`' <br /> ---------------------- <br /> AUG <br /> Customer : D . S . Sprint Date : 8/6E WRU-MENTAL HEALTH <br /> PERMIT/SERVICES <br /> Address : 6855 W . 8 Mile Rd . City : Stockton <br /> Product Type : Diesel Tank Gallons : 6000 'Tank # : 1 <br /> Test Results - 60 Minute Temperature Cogparison <br /> Starting Time For Temperature Check 10 : 00 -- Completion 'rime 11 : 00 <br /> 1 . Weighted Temperature - Finish . . . . . . . . . . . . . . . . . . . . . . = 71 . 4025 <br /> 'L . Weighted 'Temperature - Start . . . . . . . . . . . . . . . . . . . . . . . = 7,1 . 4000 <br /> 3. Weighted Temperature Change ( 2 from 1 ) . . . . . . . . . . . . . . _ + . 003 <br /> 4 . Volume Change for Each Degree of Temperature Change = 2 . 730 <br /> 5 . Volume Change Due To Temperature ( 3 x 4 ) . . . . . . . . . . . . = 1 . 008 <br /> Test Results - 60 Minute Volume Comparison <br /> Starting Time For Volume . . . . . Check 10 : 00 - Completion Time 11 : 00 <br /> 6 . Volume of Product Added (+) or Removed (-) During the test <br /> to Return "Test Level Indicator " to Starting Point = t . 012 <br /> 7 . Leak Rate (gallons/hour) Add line 5 to line 6 . . . . . . . _ + . 020 <br /> This leak rate DOES NOT exceed the standard of 0 . 050 gallons per hour <br /> described in the National Fire Protection Association , Bulletin <br /> N . F . P . A . 320 . <br /> 8 . Comments : THE TANK IS TIGHT K THE 'TANK IS NOT TIGHT ___ <br /> All of the information used to determine the above results is true <br /> and accurate to the best of my knowledge and has been developed by <br /> using methods and procedures of the "SOILTEST Tank ' Tegrity Tester" . <br /> Certified Technician ___. ___ � A. .._.______Cert . <br />