Briana Armstrong <br /> From: Aris Cacapit [EH] <acacapit@sjcehd.com> <br /> Sent: Tuesday,January 22, 2013 4:41 PM <br /> To: Briana Armstrong <br /> Cc: Thuy Tran [EH]; Garrett Backus [EH]; Raymond von Flue [EH]; Willy Ng [EH]; Kasey Foley <br /> [EH] <br /> Subject: Costo Lubrizol updates <br /> Good Afternoon Briana, <br /> Monitoring Plan must indicate in section X. that the spill container for the manuel transfer pump operation must describe <br /> the means in which it will be kept empty per CCR2635(b)(1). (For Garrett, Thuy, &Aris) <br /> The service request page for the install and retrofit permits are signed by Costco. The Application For Underground <br /> Storage Tank Installation Permit is signed by Costco and Barghausen. The Application For Underground Storage <br /> Tank Retrofit or Piping Repair Permit is also signed by Costco and Barghausen. The Service Request Page and <br /> Application must all be signed by Costco or Bargausen. (Preferably Costco). <br /> Site Map T-3 Section E part 54 & 60 lists Fiberglass Systems 3" over 2" FRP. Fiberglass Systems should be changed to <br /> Ameron Dualoy. <br /> Site Map T-4 part 33 should list hydrostatic sensor-dual POINT float, with 4" NPT male adapter(for hydrostatic tank <br /> monitor). <br /> Site Maps that list the mechanical flapper at 95% should be changed to 90%. <br /> Submit a copy of the Lubrizol compatibility letter for Blueline. <br /> Site Maps T-1 &T-2 list the drop tube with mechanical flapper to be installed at 95% overfill prevention. Change 95% to <br /> 90%. <br /> Resubmit updated documents/site maps. <br /> Thank you, <br /> Aris Cacapit, REHS <br /> San Joaquin County Environmental Health Department <br /> 1868 E. Hazelton Rd. <br /> Stockton, CA 95205 <br /> desk 209 468-3453 <br /> fax 209 468-3433 <br /> email acacapit(a).sicehd.com <br /> 1 <br />