Water Boards: LG 113 <br />• <br />C <br />Welcome to <br />California' <br />Issue Date: November 22, 1995 <br />Revision Date: March 28, 2002 <br />Veeder-Root <br />Page 1 of 2 <br />TLS 350, 350PC, 350R, 350RPC, 350PIus, Red Jacket ProMax Leak Detector, Series 845 <br />AUTOMATIC ELECTRONIC LINE LEAK DETECTOR <br />Certification Leak rate of 3.0 gph at 10 psi* with PD = 100% and PFA = 0%v. <br />Leak rate of 0.2 gph at operating pressure with PD = 100% and PFA = 0%. <br />Leak rate of 0.1 gph at 1.5 times operating pressure* with PD = 100% and PFA = 0%. <br />*Since leak rate varies as a function of pressure, this leak rate and pressure were certified u <br />equivalent leak rate and pressure, in accordance with an acceptable protocol. <br />Leak 1.88 gph for leak rate of 3.0 gph. <br />Threshold 0.17 gph for leak rate of 0.2 gph. <br />0,05 gph for leak rate of 0.1 gph. <br />A pipeline system should not be declared tight if the test result indicates a loss that equals c <br />this threshold. <br />Applicability Gasoline, diesel, aviation fuel. <br />Other liquids may be tested after consultation with the manufacturer. <br />Specification System tests pressurized fiberglass and steel pipelines. <br />Tests are conducted at operating pressure. <br />System will not function with a mechanical line leak detector installed in the pipeline. <br />Pipeline Maximum of 98.4 gallons. <br />Capacity <br />Waiting Time None between delivery and testing. <br />Minimum of 16 minutes between dispensing and testing for leak rate of 3.0 gph. <br />Minimum of 45 minutes to 1 hour between dispensing and testing for leak rate of 0.2 gph. <br />Minimum of 2 hours, 30 minutes between dispensing and testing for leak rate of 0.1 gph. <br />Test Period Response time is 28.8 seconds for leak rate of 3.0 gph. <br />Response time is 32 to 48 minutes for leak rate of 0.2 gph. <br />Response time is 18 minutes for leak rate of 0.1 gph. <br />Test data are acquired and recorded by a microprocessor. <br />Calculations are automatically performed by the microprocessor. <br />System Permanent installation on pipeline. <br />Features Automatic testing of pipeline. <br />Preset threshold. <br />Single test to determine if pipeline is leaking. <br />Pump shutdown (optional), message display and alarm activation if leak is declared. <br />http://www.waterboards.ca.gov/cwphome/ust/leak_prevention/lgl 13/Vendor—Files/veeder... 2/13/2008 <br />