Laserfiche WebLink
J <br /> SY R~ <br /> w <br /> TEST DATA AND <br /> TEST RESULTS <br /> July 14 , 1987 <br /> Butch Kishida <br /> Kishida Trucking <br /> 1725 Ackerman Drive <br /> Lodi., California 95240 <br /> Bear Butch: <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank (s) . <br /> Attached are copies of the test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency . <br /> A tank system is considered tight , according to the current <br /> rules, if the gain is less than .02 or the loss is less than . 05 <br /> gallons per one hour of testing. If the results are beyond these <br /> parameters , you should consider taking some remedial action. <br /> TANK #/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> 1, 000 Diesel Fuel +. 00412 Yes <br /> 550 Diesel Puel -. 00196 Yes <br /> Please contact us if you need additional assistance or <br /> information . <br /> Sincerely, <br /> W. Savage <br /> Certified Tester <br />