Laserfiche WebLink
0 0 <br /> 5. Contact Ray von Flue(468-9848)to arrange the following inspections(a 48-hour notice <br /> is required): <br /> a. Witness the hydrostatic test for 60 minutes(or equivalent) once concrete has set. <br /> b. Verify direct bury spill container has corossion protection and five gallon <br /> capacity before back filling. <br /> c. Verify drain valve functionality. <br /> 6. Since concrete will be broken near the UST,a secondary containment test must be <br /> performed on the UST once concrete is poured in accordance with the manufacturer's <br /> guidelines. Results must be received by EHD within seven days of returning the facility <br /> to operating condition. <br /> 7. An"Underground Storage Tank Certification of Installation/Modification" form shall be <br /> submitted by the owner or the owners'agent [pursuant to(CCR)2635(d)] before this <br /> upgrade will be considered complete by EHD. <br /> 8. This permit expires 180 days from the approval date. <br /> Ray von Flue,REHS <br /> Senior Registered Environmental Health Specialist <br />