r t • <br /> • <br /> INDIVIDUAL TANK INFORMATION AND TEST RESULTS <br /> i Tanknobgy <br /> TEST DATE:10/31/01 8900 SHOAL CREEK,BUILDING 200 WORK ORDER NUMBER2219144 <br /> CLI€NT:VERTEX SERVICES, LLC AUSTIN,TEXAS 78757(512)451-5334 SITE:RYDER 1071A <br /> TANK INFORMATION <br /> Tank ID: 1/MAIN 1 Tank manifolded: YES Bottom to top fill in inches: 168.8 <br /> Product: DIESEL Vent manifolded: YES Bottom to grade in inches: <br /> Capacity in gallons: 12,110 Vapor recovery manifolded: NO Fill pipe length in inches: 72.8 <br /> Diameter in inches: 96.00 Overfill protection: YES Fill pipe diameter in inches: 4.0 <br /> Length in inches: 391 Overspill protection: YES Stage I vapor recovery: NOME <br /> Material: DW STEEL Installed: ATG Stage It vapor recovery: NONE <br /> CP installed on: <br /> COMMENTS <br /> TANK TEST RESULTS Test Method:VacuTect LEAK DETECTOR TEST RESULTS Test method: FTA <br /> Dipped Water Level: Start(an) End(in) New/passed Failed/replaced New/passed Failed/replaced <br /> L.D.#1 L.D.#1 L.D.#2 L.D.#2 <br /> Dipped Product Level: <br /> Probe Water Level: Make: RED JACKET <br /> Ingress Detected: Water Bubble Ullage Model: X.L.D. <br /> S/N; 30190-0009 <br /> Test time: Open time in sec: 3.00 <br /> Inclinometer reading: Holding psi: 15 <br /> VacuTect Test Type: NOT Resiliency cc: 210 NOT <br /> VacuTect Probe Entry Point: TESTED Test leak rate ml/m: 189.0 TESTED <br /> Pressure Set Point: Metering psi: 30 <br /> Tank water level in inches: Calib. leak in gph: 3.00 <br /> Water table depth in inches: Results: PASS <br /> Determined by(method): <br /> Result: COMMENTS <br /> COMMENTS <br /> LINE TEST RESULTS Test type: TLD-1 <br /> LINE A B C D <br /> Material: DW FIBERG <br /> Diameter(in): 2.0 <br /> Length(ft): 100.0 <br /> Test psi: 50 <br /> Bleedback cc: 80 <br /> Test time(min): 30 NOT NOT NOT <br /> Start time: 10:36 TESTED TESTED TESTED <br /> End time: 11:06 <br /> Final gph: 0.006 <br /> Result: PASS <br /> Pump type: PRESSURE <br /> Pump make: RED JACKET <br /> COMMENTS Impact Valves Operational: YES <br /> Printed 11/15/2001 12:55 <br />