Laserfiche WebLink
' 1 <br /> tO Tdnk1701 gy <br /> 8900 SHOAL CREEK,BUILDING 200 <br /> AUSTIN,TEXAS 78757 <br /> (512)451-6334 <br /> FAX(512)459-1459 <br /> TEST DATE:10/31/01 WORK ORDER NUMBEM219144 <br /> CLIENT:VERTEX SERVICES, LLC SITE:RYDER 1071A <br /> COMMENTS <br /> Reserve die tank has .5 inch water in annular. <br /> New oil sump needs to be cleaned out. <br /> Satellite lines not tested, cannot isolate main dispenser meter hose and nozzle from line impact <br /> valves on satellite side, need impact or ball valve on main dispenser side also. <br /> Main line tested to impact on main dispenser on both lines. <br /> PARTS REPLACED <br /> QUANTITY DESCRIPTION <br /> HELIUM PINPOINT TEST RESULTS (IF APPLICABLE) <br /> ITEMS TESTED <br /> HELIUM PINPOINT LEAK TEST RESULTS <br /> Printed 1111512001 12:55 KOHLMEYER <br />