Laserfiche WebLink
From: 011222t)D9 17:D4 #347 P.008/Oil <br />6 N T R r. <br />BAIA C H <br />8, SPILL/OVERFILL CONTAINMENT BOXES <br />Facility is Not Equipped W ith Spill/Overfill Containment Boxes <br />.- <br />Spill/Overfill Containment Boxes are Present, but were Not Tested <br />Test Method Developed By: <br />1 -Spill Bucket Manufacturer X Industry Standard r-^ Professional Engineer <br />I Other (Specify) <br />Test Method Used: <br />°_j Pressure <br />I Other (Specify) <br />Vacuum X Hydrostatic <br />Test Equipment Used: Ronan/Caldwell Hydrostatic 'Sump Tester Equipment Resolution: 0.0000Y' <br />Neo. Oil Waste Oil Main Diesel Reserve <br />Diesel <br />Bucket Diameter: <br />127, 12" <br />12., <br />12" <br />Bucket Depth: <br />13" 13.5" <br />13.5" <br />15" <br />Wait time between applying <br />pressure/vacuunVwater and <br />starting test; <br />Test Start Time: <br />11:30 am 11:30 am <br />12:30 pm <br />12:30 pm <br />Initial Reading (R,): <br />Test End Time: <br />12:00 pm 12:00 pm <br />1:00 pin <br />1:00 pm <br />Final Reading (Rr.): <br />Test Duration: <br />30 min. <br />Change in Reading (RF:-Rl): <br />0 0 <br />U 0 <br />Pass/Fail Threshold or <br />Criteria: <br />PASS =No Loss or Lass of 0.0020" or less in 30 minutes <br />Test Result: <br />Pass <br />Comments — (inchide irrfonnation on repairs made prior to testing, a)td recommendGcl,foll(iiv-up.foi-.failed tHsts) <br />Note: Caldwell Sump Tester used for hydrostatic test. <br />