Laserfiche WebLink
..i <br />Triangle Environmental, Inc. <br />2525 West Burbank Blvd., Burbank, CA 91505-2302 <br />(818) 840-7020 (818) 840-6929 <br />UST TESTING SYSTEMS SUMMARYSHEET <br />Precision Underground Storage Tank System Leak Test <br />Client: <br />Tosco Marketing Co. Tosco Facility # 05643 <br />3550 North Central Avenue <br />Phoenix, Az 85012- Test Date 5/18/98 <br />Carmen Tucker <br />(602)200-4530 <br />Facility: <br />Work #: <br />340690 <br />Tosco Facility # 05643 <br />County: <br />SAN JOAQUIN <br />1502 NORTH EL DORADO <br />Cross Street: <br />STOCKTON, CA 95204 <br />Tank <br />Test System <br />Tank <br />Line <br /># Product Capacity <br />Type <br />Rate/Results <br />Ullage Result <br />Rate/Result <br />L/D Result <br />I Unleaded Regular 11855 <br />System 5000 <br />0.020 PASS <br />PASS <br />-0.021 PASS <br />PASS <br />2 Unleaded Premium 11855 <br />System 5000 <br />0.020 PASS <br />PASS <br />-0.032 PASS <br />PASS <br />3 Diesel 11855 <br />System 5000 <br />0.020 PASS <br />PASS <br />-0.021 PASS <br />PASS <br />Certified By:Technician: Tony Kiani <br />State Lic. #s: CA -1049 <br />1 % M(gr's #: TEI-047 <br />Comments: <br />Compliance test ALL <br />This precision tank testing system has been third party evaluated according to the guidelines of the EPA <br />procedures for annual leak detection systems and found to exceed the criteria of detecting a leak of 0.10 <br />gph with a Pd >95% and Pfa <5% as required by Local, State and Federal EPA UST Technical Standards <br />Part 280 for precision testing systems. <br />