Laserfiche WebLink
, <br /> d. Spill/Overfill Containment Boxes <br /> Test Method Developed By: ❑Tank Manufacturer ❑x Industry Standard ❑Professional Engineer <br /> Test Method Used: ❑Pressure ❑Vacuum 0 Hydrostatic <br /> Test Equipment Used: Incon TS STS Leak Detector Equipment Resolution:±0.002 <br /> Spill Box# 871 Spill Box# 872 Spill Box# 91 Spill Box# <br /> ucket Diameter: <br /> Bucket Depth: 14" 14" 14" <br /> Wait time: 15 min 15 min 15 min <br /> Test Start Time: 9:06 AM 9:06 AM 9:06 AM <br /> Initial Reading: 3.3148 2.8581 2.8577 <br /> Test End Time: 9:21 AM 9:21 AM 9:21 AM <br /> Final Reading: 3.3147 2.8579 2.8570 <br /> Test Duration(hh:mm): 00:15 00:15 00:15 00:00 <br /> Change in Reading: -0.0001 -0.0002 -0.0007 0.0000 <br /> Pass/Fail Threshold or Criteria: ±0.002 ±0.002 ±0.002 ±0.002 <br /> Test Result: * Pass O Fail *Pass O Fall *Pass O Fail <br /> Comments: <br /> 2 of 2 <br />