Laserfiche WebLink
INDIVIDUAL TANK INFORMATION AND TEST RESULTS <br /> _-NIP TankrxWOW <br /> TEST DATE:02/09/10 8501 N MOPAC EXPRESSWAY,SUITE 400 WORK ORDER NUMBER2272103 <br /> CLIENT:VALERO AUSTIN,TEXAS 78759(512)451-6334 SITE:ULTRAMAR 3698 (VALERO) <br /> F, TANK INFORMATION <br /> Tank ID: MAIN 2 Tank manifolded: YES Bottom to top fill in inches: 137.5 <br /> Product: UNLEADED Vent manifolded: YES Bottom to grade in inches: 146.0 <br /> Capacity in gallons: 10,152 Vapor recovery manifolded: YES Fill pipe length in inches: 41.5 <br /> Diameter in inches: 96.00 Overfill protection: YES Fill pipe diameter in inches: 4.0 <br /> Length in inches: 328 Overspill protection: YES Stage I vapor recovery: DUAL <br /> Material: DN STEEL Installed: ATG Stage II vapor recovery: ASSIST <br /> CP installed on: <br /> COMMENTS <br /> 1TANK TEST RESULTS Test Method:VacuTect LEAK DETECTOR TEST RESULTS Test method: LOT-5000 <br /> Start(in) End(in) New/passed Failed/replaced New/passed Failed/replaced <br /> Dipped Water Level: L.D.#1 L.D.#1 L.D.#2 L.D.#2 <br /> Dipped Product Level: <br /> Make: RED JACKET <br /> Probe Water Level: <br /> Model: Fx1v <br /> Ingress Detected: Water Bubble Ullage S/N: 5019 <br /> Test time: Open time in sec: 3.00 <br /> Inclinometer reading: Holding psi: 15 <br /> VacuTect Test Type: NOT Resiliency cc: 65 NOT <br /> VacuTect Probe Entry Point: TESTED Test leak rate ml/m: 189.0 TESTED <br /> Pressure Set Point: Metering psi: 13 <br /> Tank water level in inches: Calib. leak in gph: 3.00 <br /> Water table depth in inches: Results: PASS <br /> Determined by(method): <br /> Result: COMMENTS <br /> COMMENTS <br /> LINE-TEST RESULTSTest type: TLD-1 <br /> LINE A D <br /> 111P,B <br /> Material: DW FIBERG <br /> Diameter(in): 2.0 <br /> Length (ft): 150.0 <br /> Test psi: 50 <br /> Bleedback cc: 5 <br /> Test time(min): 30 NOT NOT NOT <br /> Start time: 11:35 TESTED TESTED TESTED <br /> End time: 12:05 <br /> Final gph: 0.000 <br /> Result: PASS <br /> Pump type: PRESSURE <br /> Pump make: RED JACKET <br /> COMMENTS Impact Valves Operational: YES <br /> Printed 02/17/2010 09:22 <br />