• • RECEIVED <br /> L, Z tit,L 3 14 <br /> LICIT 5000 Field Test Apparatus ENVIROP�i011IT L <br /> Tanknology Line Leak Detector Test <br /> HEALTH DEPARTMEN <br /> Work Order: 2314728 Date: 2/4/2014 <br /> Site Name/ID: CORNER STORE#36981 3698 <br /> Address: 153 E 11TH ST QC-D-3 <br /> City: TRACY State: CA Zip: 95376 <br /> Tank ID T1 T3 <br /> Product UNLEADED PREMIUM <br /> Product Line 1 1 <br /> Tested From 6 6 <br /> xislinglNew Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical <br /> ManufacturerlModel Red Jacket FX1 Red Jacket FX1 <br /> Serial No. 5019 4578 <br /> Pump Operating Pressure(psi) 26.00 40.00 <br /> alibrated Leak(mllmin) 189.0 189.0 <br /> alibrated Leak(gph) 3.00 3.00 <br /> Holding PSI 15.00 20.00 <br /> NIA for Electronic Lo's <br /> --- <br /> Resiliency(ml) 100.00 100.00 <br /> NIA for Electronic LD's <br /> Metering PSI g 12 <br /> NIA for Electronic Lo's <br /> pening Time(sec) 3 2 <br /> NIA for Electronic LD's <br /> est Results Pass Pass <br /> Technician Comments: <br /> Technician Name: Darren Sciume Certification#: 103637 <br /> Expire Date: 7/28/2016 <br /> Technician Signature: <br /> Environmental Compliance for Petroleum Systems <br /> 0 2014 Tarmc!Ny Inc.,Au54n,TX. All right reserved Wrl1 degy.000 <br />