Laserfiche WebLink
PART III <br /> SECTIONS VI & VII: SHOULD BE COMPLETED BY <br /> THE UST INSPECTOR PRIOR TO THE VISIT. <br /> SECTION VI : METHODS TO CONTROL POTENTIAL HEALTH & SAFETY HAZARDS. <br /> MONITORING INSTRUMENTS: (NOTE: MONITORING INSTRUMENTS MUST BE USED FOR ALL <br /> OPERATIONS UNLESS APPROPRIATE RATIONALE OR RESTRICTIONS ARE PROVIDED). <br /> ORGANIC VAPOR ANALYZER ( ) <br /> PHOTOIONIZATION DETECTOR ( ) <br /> COMBUSTIBLE GAS INDICATOR (CGI) <br /> OXYGEN METER �) <br /> HYDROGEN SULFIDE METER ( ) <br /> DETECTOR TUBES (SPECIFY) ( ) <br /> OTHER (SPECIFY TOXIC GAS, AIR SAMPLING PUMPS, ETC.) ( ) <br /> LOCATION OF NEAREST FIRE EXTINGUISHER (ON ALL TRUCKS) (�() <br /> NEAREST WATER (ON SITE) ( ) <br /> IF MONITORING INSTRUMENTS ARE NOT USED, SPECIFY RATIONALE OR JUSTIFICATION OR <br /> ACTIVITY/AREA RESTRICTIONS. <br /> ACTION LEVELS (BREATHING ZONE): <br /> COMBUSTIBLE GAS INDICATOR <br /> 0-10% LEL NO EXPLOSION HAZARD <br /> 10-25% LEL POTENTIAL EXPLOSION HAZARD; NOTIFY SITE HEALTH & <br /> SAFETY OFFICER <br /> >25% LEL EXPLOSION HAZARD; INTERRUPT TASK/EVACUATE <br /> OXYGEN METER <br /> <21.0% 02 OXYGEN NORMAL <br />