0 0 <br /> Pacific Bell: 2600 Camino Ramon, Room 313000, San Ramon, CA 94583 <br /> ROUTINE MONITORING PROCEDURES <br /> Section 2632(d)(1)Title 23 CCR,Chapter 16 <br /> UNDERGROUND FUEL STORAGE TANK <br /> FacilityName: Pacific Bell (UE148) <br /> Facility Address: 7717 S. ELM ST.,FRENCH CAMP <br /> UST Installed: Double Wall Composite 2,000 Gallons Containing Diesel Fuel for the Emergency <br /> Generator. <br /> Piping Installed: Double Wall "Enviroflex" non-metallic flexible piping system for the product <br /> supply and return lines. <br /> A. The Frequency of Performing the Monitoring: <br /> Monitoring is performed continuously on the: <br /> • Double wall UST Interstitial space and the piping sump. <br /> B. The methods and equipment used to perform continuous monitoring are: <br /> • VEEDER ROOT UST Monitoring System Model#TLS-350 <br /> • Site fax modem <br /> • GPH magnetostrictive in-tank volumetric probe Model# 847390-107 <br /> • Floating liquid sensors in the: <br /> 1. UST Annular space sensor Model# 794390-420 <br /> 2. Piping sump sensor Model# 794380-208 <br /> 3. Tank Overfill Model # 790091-001 <br /> 1:\HAZMAT%PACBFLL\F0RMS\SBC Monimr Plan Meme. o <br /> Printed: December 6, 2001 page 2 <br />