Laserfiche WebLink
Veeder-Root California Edition:June 2001 <br /> • <br /> TLS-300C, 3001, 300PC, 350, 350PC, 350R, 350RPC <br /> Solid-State Pan/Sump Sensor(794380-321, 351), <br /> Piping Sump Sensor(794380-208, 209), <br /> Micro Sensor(794380-340) <br /> LIQUID-PHASE INTERSTITIAL DETECTOR <br /> Detector: <br /> Output type: qualitative <br /> Sampling frequency: continuous <br /> Operating principle: product permeable, ultrasoniGfloat switch <br /> Test Results: <br /> Piping Sump Sensor(794380-208, 209) unleaded gasoline diesel water <br /> Minimum product level (cm) 3.51 3.40 3.03 <br /> Precision 0.011 0.011 0.011 <br /> Detection time (sec) <1 <1 <1 <br /> Solid-State Pan/Sump Sensor(794380-321, 351) <br /> Minimum product thickness (cm) 2.60 2.50 2.60 <br /> Precision 0.010 0.010 0.010 <br /> Detection time (sec) <1 <1 <1 <br /> Micro Sensor(794380-340) <br /> Minimum product thickness (cm) 0.51 0.46 0.48 <br /> Precision 0.011 0.007 0.007 <br /> Detection time (sec) <1 <1 <1 <br /> Comments: <br /> Sensors are reusable. <br /> 208 and 209 sensors are also compatible with 300 series. <br /> Veeder-Root Evaluator: Ken Wilcox Associates, Inc. <br /> 125 Powder Forest Dr. Tel: (816)443-2494 <br /> Simsbury, CT 06070-2003 Dates of Evaluation: 10/20/94 <br /> Tel: (860) 651-2700 <br /> 266 <br /> Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the _ <br /> performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and <br /> regulations. <br />