SWRCB,January 2002 Page S of 8 <br /> 9. SPILL/OVERFILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes U <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested U <br /> Test Method Developed By: U Spill Bucket Manufacturer ill Industry Standard U Professional Engineer <br /> U Other(Specify) <br /> Test Method Used: U Pressure U Vacuum Xl Hydrostatic <br /> U Other(Spec) <br /> Test Equipment Used: Visual Equipment Resolution: <br /> R Spill Box# 1 ulp Spill Box#2 P l u sSpill Box#3 Spill Box# <br /> Bucket Diameter: 12" 12" 12" <br /> Bucket Depth: 1211 <br /> 1211 <br /> 1 2" <br /> Wait time between applying <br /> pressure/vacuum/water and N/A N/A N/A <br /> starting test: <br /> Test Start Time: 9:00 9:00 9:00 <br /> Initial Reading(R,): 0 0 0 <br /> Test End Time: 2.00 2. 00 2. 00 <br /> Final Reading(Rr): 0• 0 • 0 <br /> Test Duration: 5 hrs. 5 hrs. 5 hrs. <br /> Change in Reading(R,R,): 0 0 0 <br /> Pass/Fail Threshold or <br /> Criteria: 0 Loss 0 Loss 0 Loss <br /> Teat Result: IX Pass U Fail XJ Pass U Fail X Pass U Fail U Pass U Fan <br /> COnlnlentS— (include information on repaiis made prior to testing dad recommended folloxlup forfailed tests) <br /> Please direct any comments regarding this form to: <br /> SWRCB UST Program,Attn: Scott Bacon <br /> 1001 "I"Street,Box 944212 <br /> Sacramento,CA 95814 <br /> Phone:(916)341-5873,Fax:(916)341-5808 <br /> e-mail:bacons@cwp.swrcb.ca.gov <br />