1 . These plans are for the installation of new gasoline 'facilities only,.
<br /> Street improvements, store expansion, and landscaping to 'be done by
<br /> others.
<br /> 2. All asphalt is to be replaced with minimum 6" baserock and minlmum �5"
<br /> asphalt. Parking lot work to be done In two sections so, at no time. is
<br /> entire parking shut down to customers.
<br /> 3. All work shall conform to the requirements of
<br /> Environmental Health Services, and all applicable
<br /> Federal , State, and local codes, ordinances and regulations.
<br /> 4 . before the underground tanks are placed in the ground, a holiday test o � '
<br /> shall. be performed on each tank, Test shall be performed by the
<br /> contractor at site. Owner representative shall be notified as to when
<br /> tanks arrive, so test can be witnessed by owner representative.
<br /> S. Inc contractor shall arrange for inspections by local , state, and JLA
<br /> federal agencies as required by these agencies, during the points of
<br /> construction as required.
<br /> o. all wiping shall be new, Product, vent, and vapor piping shall be 2"
<br /> fiberglass Piping•
<br /> All above ground vent risers shall be 2" schedule 40 galvanized piping. 940 .;SFUD1023
<br /> Ictach new vent risers securely to existing building with preforrne,l
<br /> Pipe clamps. t
<br /> (707)745-0502
<br /> 3. Yeoz and vapor recovery piping shall be installed to slope down contin-
<br /> luusly toward tanks at a minimum slope of 1/8' per foot.
<br /> 3'
<br /> a. all piping runs are shown schematically. Contractor shall install
<br /> .,: 1 lines in the most economical manner possible to reduce lengths of
<br /> runs, number of fittings, and maximize slope of vent and vapor piping.
<br /> v. n, ,allation of electrical conduits, including all Junction boxes,
<br /> ,.undult seals, wiring, etc. shall be performed by the Customer Co. 's
<br /> Forces. ' Gasoline contractor shall provide all trenching for electrical I
<br /> _inducts required for tank and dispenser installation. Wherever possible,
<br /> :.ectrical conduits shall be installed in a common trench with piping ,
<br /> m>.;: ine contractor shall coordinate all work with the store contractor,
<br /> jnopy contractor and the Customer Company. Canopy contractor for .
<br /> this Job will be ' Rankin and Rankin, Don Rankin, (916)823-9525.
<br /> j. .: Ine contractor shall remove existing island, dispensers, light
<br /> �, .d guard posts, drive slab, tanks, and piping. Customer company F_0_0D_&_LIQUOR 37_
<br /> will remove fromi the site the dispensers and light poles. The gasoline t
<br /> -,ntractor shall dispose of everything else.
<br /> 15 West G ra ntflrle
<br /> ...,. : ine contractor shall install three (3) new 12,000 gallon Modern Tracy, Ca
<br /> n.:lding double containment tanks to be furnished by the Customer Company.
<br /> Delivery time of tanks shall be coor'dinated by the gasline contractor.
<br /> ,. .._,. : ine contractor shall install new Red Jacket submersible turbine
<br /> . -ws, pit boxes, and leak detectors furnished by the Customer Company. The Customer Co
<br /> �soline contractor shall provide and install tank hold down deadmen PO. BOX 886 Benicia , Ca
<br /> -:,.d anchors if required due to high water table at time of construction.
<br /> f
<br /> .soline contractor shall construct new canopy column footings. Canopy
<br /> -.bricator shall Provide approved footing details and plans and anchor
<br /> )alts. Canopy contractor shall erect canopy under separate contract.
<br /> SHEET TITLE
<br /> ine contractor shall Provide and install all products, vent and vapor SCOPE OF WORK
<br /> )Ing, manways, risers, etc. unless noted otherwise on these plans.
<br /> 'he gasoline contractor shall Provide holes in the island :and stub up
<br /> Ing to suit the dispenser manufacturer's requirements. The gasoline
<br /> . ,itractor shall- install dispensers on formed island and connect product REVISIONS DATE
<br /> Jing. Electrical connection to be made. by the Customer Company , SION
<br /> _
<br /> 'Ane contractor shall construct new 6" concrete tank and drive slab
<br /> '. nfurced with #3 rebar a 18" D.C. each way. All concrete for slabs
<br /> inJ pump island shall be colored black with 8 lbs. of color per yard,
<br /> nish concrete with a medium broom finish. noy
<br /> Date Drawn By
<br /> Job No. Checked By
<br /> SHEET
<br /> )F WORK =r o
<br /> OF SHEETS
<br />
|