TESTING: NOTES:
<br /> 100 OHMS MAXIMUM CAUTION: AVOID CONNECTING ANY ELECTRICAL TEST ALL STAGE I FILL AND VAPOR RISER ADAPTERS
<br /> 2 POINT GROUND-EARTH LEAD TO THE FILL OR VAPOR RISER IN A MANNER SHALL BE ELECTRICALLY GROUNDED TO PROMOTE
<br /> RESISTANCE THAT WOULD POTENTIALLY PRODUCE STATIC THE RELAXATION OF STATIC CHARGE.
<br /> UNDERGROUND COMPOSITE DISCHARGE OR SPARKS OF ANY KIND,
<br /> STORAGE TANK ASSEMBLY METAL HIGH RESISTANCE OR NON--CONDUCTIVE FLUID
<br /> ASSEMBLY THE FILL AND VAPOR RISERS SHALL BE TESTED FLOWING THOUGH PIPING CAN GENERATE STATIC
<br /> O AFTER INSTALLATION AND PERIODICALLY TO VERIFY CHARGES CAPABLE OF IGNITING FUEL VAPORS.
<br /> BONDING AND GROUNDING COMPETENCY. PROPER BONDING AND GROUNDING OF THE FILL
<br /> � GROUND 'i" AND VAPOR RISER ASSEMBLIES ARE NECESSARY 't0
<br /> BONDING CONNECTOR INDEPENDENT THE MAXIMUM RESISTANCE FROM ANY FILL OR ASSURE SAFE FILLING OPERATIONS.
<br /> JUMPER -- GROUND VAPOR ADAPTER TO THE BODY OF THE GROUND
<br /> ROD SHALL NOT EXCEED 10 OHMS FOR A THE BONDING AND GROUNDING FOR STATIC
<br /> 100K OHMS METALLIC RISER PIPE, SPILL CONTAINMENT AND ELECTRICITY PROTECTION SHALL BE IN COMPLIANCE
<br /> SUMP MAX. ADAPTER ASSEMBLIES. PER ALL APPLICABLE FEDERAL, STATE AND LOCAL
<br /> CODES INCLUDING NFPA 30, FLAMMABLE AND
<br /> THE RESISTANCE THROUGH ANY COMPOSITE OR COMBUSTIBLE LIQUIDS CODE, NFPA 77,
<br /> NONMETALLIC STAGE 1 CONTAINMENT FITTING SHALL RECOMMENDED PRACTICE ON STA11C ELECTRICITY,
<br /> BE MEASURED WITH A OHMMETER CAPABLE OF NFPA 70, NATIONAL ELECTRIC CODE, AND THE
<br /> READING UP TO 10 MEGAOHMS. PER THE SHELL CALIFORNIA CODE OF REGULATIONS, SUBCHAPTER
<br /> STANDARD, THE SUM COLLECTIVE RESISTANCE OF 15, PETROLEUM SAFETY ORDERS-REFINING,
<br /> THESE SEMI-CONDUCTIVE ELEMENTS SHALL NOT TRANSPORTATION AND HANDLING, ARTICLE 5, FIRE
<br /> EXCEED 100,000 OHMS. FOR THESE SYSTEMS, AND EXPLOSIONS.
<br /> THE GROUND RESISTANCE TESTER MUST BE
<br /> UNDERGROUND
<br /> CONNECTED TO THE GROUND CONDUCTOR PER SECTION 6.4.1.3 OF NEPA 77, THE MEASURED
<br /> CONNECTION ON THE COMPOSITE CONTAINMENT TOTAL RESISTANCE IN THE GROUND PATH TO EARTH
<br /> STORAGE TANK TESTING BURIED GROUND ROD SYSTEM SYSTEM OR RISER PIPE. SHALL BE LESS THAN 1 MEGAOHM WHICH IS
<br /> CONSIDERED ADEQUATE FOR RELAXATION OF STATIC
<br /> (EXISTING ING SIZES FOR INSTALLATIONS WITHOUT AN EXPOSED GROUND CHARGE. THE MAXIMUM ALLOWABLE GROUND PATH
<br /> 1 L ROD CONNECTION, TOTAL SYSTEM RESISTANCE TO EARTH RESISTANCE FOR STATIC ELECTRICITY
<br /> GROUND SHALL BE MEASURED WITH A GROUND RESISTANCE GROUNDING APPLICATIONS FOR SHELL OIL
<br /> BONDING CONNECTOR TESTER BY A QUALIFIED ELECTRICIAN FAMILIAR WITH PRODUCTS US STATION SITES SHALL NOT EXCEED
<br /> JUMPER GROUND TESTING. THE TWO POINT METHOD MAY 100;000 OHMS,
<br /> BE USED WITH THE SITE ELECTRICAL GROUNDING
<br /> SUMP 10 OHMS AS THE SECOND TEST POINT. PER SECTION 6.4.1.3 OF NFPA 77, THE
<br /> MAX. RESISTANCE IN METALLIC BONDING AND OR
<br /> THE NEC MAXIMUM GROUND PATH RESISTANCE FOR GROUNDING SYSTEMS SHALL BE LESS THAN 10
<br /> COMPOSITE TEST LEAD CONNECTED CURRENT CARRYING APPLICATIONS IS 25 OHMS. OHMS. RESISTANCE HIGHER THAN 10 OHMS
<br /> ASSEMBLY METAL TO GROUND ROD, NOT HOWEVER, GROUND ROD TO EARTH RESISTANCE UP INDICATES INADEQUATE CONNECTIONS,
<br /> LUG OR WIRING
<br /> ASSEMBLY _— TO 100 OHMS SHALLBE ACCEPTABLE PER THE
<br /> S
<br /> SHELL STANDARD FOR STATIC ELECTRICITY A GROUNDING SYSTEM PER NEC CODE FOR
<br /> PROTECTION OF THE FILL AND VAPOR RISERS, CURRENT CARRYING CONDUCTORS SHALL BE
<br /> (� CONSIDERED MORE THAN ADEQUATE FOR A STATIC
<br /> l ELECTRICITY GROUNDING SYSTEM,
<br /> UNDERGROUND PER THE NFPA 30, SECTION 5-6.3.4 ALL PARTS
<br /> STORAGE 'TANK TOOK OHMS OF THE FILL PIPE ASSEMBLY, INCLUDING THE DROP
<br /> MAX. TUBE, SHALL FORM A CONTINUOUS ELECTRICALLY
<br /> CONDUCTIVE PATH.
<br /> GROUND SIZING OF THE GROUNDING AND BONDING WIRE
<br /> BONDING CONNECTOR CONDUCTORS FOR STATIC PROTECTION SYSTEMS IS
<br /> JUMPER TYPICALLY BASED ON MECHANICAL STRENGTH
<br /> RATHER THAN CURRENT CARRYING CAPACITY.
<br /> HOWEVER, PER THE CALIFORNIA CODE OF
<br /> SUMP REGULATIONS, THE MINIMUM WIRE SIZE FOR
<br /> BONDING AND GROUNDING SHALL BE COPPER AWG
<br /> P.
<br /> BACKFILL TESTING EXPOSED GROUND ROD SYSTEM A 5/8"6 BY 10' LONG COPPER CLAD STEEL
<br /> NATIVE GROUND ROD SHALL BE DRIVEN INTO NATIVE SOIL
<br /> SOILONLY. PLACING THE GROUND ROD INTO TANK PIT
<br /> v EXTREME CAUTION MUST BE OBSERVED WHILE USING ANY NON INTRINSICALLY
<br /> 8" d SAFE DEVICE IN CLASSIFIED AREAS. SUMP MUST BE TESTED POR VOLATILE PEA GRAVEL SHALL NOT BE PERMITTED UNDER ANY
<br /> PLAN VIEW tDGROUND ROD ACCESS VAPORS PRIOR TO USE, ELECTRICAL CONNECT MUST BE MACE WITH JUMPER CONDITIONS. THE CONTRACTOR IS RESPONSIBLE
<br /> COVER 0 ■ WIRE SO FINAL CONNECTION IS AWAY FROM CLASSIFIED AREAS. ■ FOR CLEARING ANY UNDERGROUND UTILITIES PRIOR
<br /> TO INSTALLATION OF THE GROUND.
<br /> THE GROUND ROD TO GROUND WIRE CONNECTION
<br /> SHALL BE ACCESSIBLE THROUGH A H-20 RATED
<br /> 8"0 MINIMUM ACCESS COVER TO ASSIST
<br /> INSPECTION, MAINTENANCE AND TESTING, THE
<br /> SCREW TYPE GROUND ROD CLAMP SHALL BE UL
<br /> LISTED FOR DIRECT BURIAL,
<br /> 2D GROUND ROD CLAMP 8" H-20 Q3 ONE STRANDED #8 THHN CONDUCTOR SHALL BE
<br /> CORD GRIP© COMPOSITE METAL ACCESS COVER RUN TO EACH FILL AND VAPOR RISER CLUSTER
<br /> CONTAINMENT CONTAINMENT CORD GRIP SLOPE CONCRETE FROM THE GROUND ROD. THE CONDUCTOR SHALL
<br /> ASSEMBLY ASSEMBLY HAVE 18" MINIMUM COVER. THE CONDUCTOR
<br /> ELBOW EX ELBOW -..q• ,,. SHALL PENETRATE THE SUMP USING A 3/4" PVC
<br /> SHOWN ROTATED 90' COATED CONDUIT AND APPROVED PENETRATION
<br /> '.• hi, " -c< FITTING. THE CONDUIT SHALL BE BENT 90' TO
<br /> •' THE VERTICAL AND TERMINATE WITH A CLASSI , DIV
<br /> CONDUCTOR • II SEAL-OFF FITTING, THREADED ELBOW AND CORD
<br /> CONDUIT GRIP FITTING. A BRONZE PIPE CLAMP SHALL BE
<br /> II CORD GRIP CONNECTED TO THE RISER PIPE 1'0 THE BONDING
<br /> MATERIAL LIST OR GROUND CONDUCTOR. TO ASSURE A
<br /> CONDUIT COMPLETE CONNECTION, ANY PAINT OR COATING
<br /> ON THE RISER SHALL BE REMOVED PRIOR TO
<br /> CORD GRIP 6 INSTALLATION OF THE GROUND CLAMP,
<br /> O '� 1 5/8"6 X 10' LONG COPPER CLAD STEEL GROUND ROD
<br /> �- GROUND LINES O GLAVEN INDUSTRIES P/N 6260613 OR EQUIV. ELECTRICAL CONDUIT, FUELING SYSTEM HARDWARE
<br /> TERMINATE 2" ABOVE #8 GROUND CONDUIT TO OTHER SUMPS OR THE STATION ELECTRICAL GROUNDING SYSTEM
<br /> HIGHEST PENETRATION FITTING CONDUCTOR CONDUCTOR PENETRATION U2 GROUND ROD CLAMP, UL LISTED FOR DIRECT BURIAL, SHALL NOT BE USED FOR GROUNDING OR BONDING
<br /> PIPE GROUND CLAMPU4
<br /> FITTING I THOMAS-BETTS P/N JAB58H OR EQUIV FILL. AND VAPOR RISERS.
<br /> ( POMECO/OPW 5110-OBVA 8" H-20 RATED ACCESS
<br /> CRIMPED GROUND COVER RISERS INSTALLED ON STEEL UST'S SHALL UTILIZE
<br /> 3/4" PVC COATEDT-��/� LUG BOLTED TO ISOLATION BUSHINGS PER THE MANUFACTURES
<br /> CONDUIT WITH SHORT HOUSING ® 4" NPT ADJUSTABLE BRONZE PIPE CLAMP, LIND INSTRUCTIONS TO PREVENT CATHODIC CORROSION.
<br /> RADIUS SWEEP NOT TO SCALE TANK - EQUIPMENT P/N JR-150-30 (905) 475-5086
<br /> NOT TO SCAL� 0 3/4" CONDULET ELBOW, CLASS 1, DIV 1, GROUP D.
<br /> 3/4" WEAVER CROUSE-HINDS P/N LBY25 OR EQUIVALENT
<br /> PENETRATION PITTING
<br /> SUMP WALL AGROUND ROD ® 3/4" NPT CORD GRIP, CROUSE-HINDS P/N CGB-292,
<br /> RANGE :1254 TO .256, ZINC STEEL
<br /> PENETRATION DETAIL ELEVATION ' VIEW DETAIL
<br /> These drawings and specifications are the confidential and I APPROVALS CALIFORNIA U.S.T STANDARDS
<br /> proprietary property of Shell Oil Products US and shoil not be 0 10 20'
<br /> copied, reproduced, disclosed, or used without Shelf Oil - DISTRICT MANAGER
<br /> Products US's written authorization. They are Intended as SHFaLl„ OIL PRODUCTS COMPANY, US STATIC ELECTRICITY PROTECTION
<br /> contract documents for use on this specific project in -- AREA TECHNICAL MANAGER
<br /> conjunction with its issue date and are not suitable for use on GRAPHIC SCALE FILL_ AND VAPOR ADAPTORS
<br /> a different project or at o later dote. 12700 Northborough Drive TERMINAL MANAGER
<br /> I 1 10 Houston TX 77067-2508 SCALE: SAP/WIC # DATE: DRAWN: REQUESTED BY;
<br /> Q Shell Oil Products, US All Rights Reserved 2002 ENGINEER STATIC- 1
<br /> REV BATE DESCRIPTION OF REVISION BY APP NONE SAP 7-31 -02 WYPER HOVLAND