Laserfiche WebLink
05/01/2004 15:23 2094se3433 FIFTH FLOOR PACIL 05 <br /> SAMPLING PROTOCOL FOR ROUTINE PIPINGIDISPENSER REMOVAUREPLACEMENT <br /> The following represents minimum Sampling criterion required for closure compliance. Soil samples collected shall be <br /> representative of native soils beneath the tank's invert (tank's bottom) at a collection depth not to exceed 2 - 4 feet. IF <br /> contamination is documented during closure, an Unauthorized Release Notification must be completed and submitted within <br /> five(5)working days pursuant to California Health &Safety Code, Section 25295. <br /> DISPENSER SAMPLES <br /> AT LEAST ONE SAMPLE BELOW EACH DISPENSER <br /> PIPING AND STOCKPILE <br /> PIPING SOIL SAMPLES 1 Sample every 20 lineal feet <br /> DISPENSER&PIPING STOCKPILE SAMPLES 2 Samples every 50 cubic yards <br /> 4 <br />