Laserfiche WebLink
09/28/2002 14:45 FAX 425 251 8782 BARGEAUSEN __ Z020 <br /> PAGE 06 <br /> 09/16/2002 07:44 523 <br /> w� IPE INC <br /> Al.ltech <br /> 17759 Bu�tt~ er~ircle, mora, CA 95370 <br /> Phone: 209-532-7320; Fax. 209-533-2650 <br /> California Tank'fester: 90-1068 <br /> California Contractor 623541 A-Haz <br /> alltech(aknlode.corn <br /> PRECISION TEST DATA SHEET for 'PIPSXG— <br /> Facility: Costco 658 Date: Sep. 12, 02 <br /> Address: 3250 Grant Line Rd. <br /> City: Tracy CA <br /> Facility contact: W.A. Craig Phone: <br /> L,I.A.: San Joaquin; Michelle L.I.A. Phone: 209-468-3451 <br /> Hasstech Accu-RM050(1) <br /> Tester <br /> Product <br /> Turbine isolation sxie od * <br /> Dispenser isolation mr-thod IMI) <br /> Test: pre are, PSI Initial linder level <br /> Final linden level 0.0490 10.0495 <br /> Time Started 1130 1200 <br /> Time Completed 1200 1230 <br /> Tot.-a test time minutes 30 130 <br /> Result: volume Gba W in GPIs 0.002 0.001 <br /> Conclusion: *lass/Fail pasts Pass <br /> Leak Detector Test: Pass pass <br /> * pass/Fail threshold is 0.0100 GPH per Manufacturer's protocol. <br /> Remarks: The line from l2ieg 1 feeds the row of islands closest to the building. <br /> The line from Reg 2 feeds the row of islands closest to the tanks- There is a <br /> crossover line that permits use of either regular turbine to feed all islands in <br /> case of a failure. Testing either line with this crossover open allows testing of <br /> all the regular lines at once. The ball valve in the crossover was closed prior to <br /> testing line leak detectors <br /> Test tech: 1�' Mike Dotten, License 98-1068 ".31612002 <br />