Laserfiche WebLink
Alltech <br /> 17759 Buttercup Circle, Senora, CA 95370 <br /> Phone: 209-532-7320; Fax: 209-533-2650 <br /> California Tank Tester: 90-1068 <br /> California Contractor 623541 A-Haz <br /> alltech@mlode.corn <br /> Precision Test Data Sheet for Line Leak Detectors <br /> Vaporless LDT-890 <br /> Facility: Costco 658 Date: Sep. 12, 02 <br /> Address: 3250 Grant Line Rd. <br /> City: Tracy CA <br /> Facility contact: W.A. Craig Phone: 707-693-2929 <br /> L.I.A.: San Joaq; Michelle L.I.A. Phone: 209-468-9847 <br /> Product 4 Re 1 Reg2 Prem <br /> Turbine manufacturer FE P FE P FE P <br /> Leak Detector mfr Red J Red J Va <br /> L.D. search pressure 10 10 20 <br /> Step-through time- seconds 4 3 3 <br /> Turbine operating ressure 38 38 38 <br /> Line holding pressure- psi 19 20 35 <br /> Bleed back test- ml 800 1100 1200 <br /> 10 psi flow _quantity- ml 95 95 95 <br /> Leak detector stays tripped? Yes Yes Yes <br /> Conclusion: * Pass/Fail Pass Pass Pass <br /> * Pass = Leak Detector stays in slow-flow during GPH Test; <br /> Fail = Leak Detector steps through to allow full pump pressure during GPH <br /> Test. <br /> Remarks: Reg 1 is the tank closest to the islands and fuels the dispenser row <br /> closest to the store. Reg 2 is the center tank and fuels the dispenser row <br /> closest to the tanks. The Premium tank fuels all dispensers. <br /> t <br /> Test tech: WzMike Dotten, License 90-10681Z,�.6/7/7002 <br />