Laserfiche WebLink
,APPENDIX B - Page 14.3 <br />The TLM will be able to detect (in the tank integrity mode) a minimum <br />of a 0.20 gallon per hour leak while compensating for temperature <br />changes within the tank with a probability of leak detection of 95 <br />percent and probability of false alarms of 5 percent; <br />The TLM system will be Level TRU (Model No. 10600) by Environment and <br />Safety, Inc., Veeder-Root TLS -350 with magnetostrictive probe, or <br />equal; <br />Install overspill protection device at the tank. The overspill <br />protection device will be Skyway (Model No. 85000), Emco Wheaton <br />A1003, or equal; <br />Install a pipeline leak detector and retrofit pressure piping system <br />with a flow restriction device. The pipeline leak detector will be <br />LR 1000 Leak Rater, Ronan X76 Line Leak Detector or equivalent. <br />GROUNDWATER <br />This facility is located within the San Joaquin Valley Groundwater Basin. <br />There is one groundwater well located approximately 0.3 miles southwest of the <br />facility. The local groundwater table elevation varies between 6 and 10 feet <br />below the ground surface. <br />