Laserfiche WebLink
IT T S Integrity Tank Testing Systems, Inc. <br /> t: TEST DATA AND <br /> TEST RESULTS <br /> vuly 19, 1988 <br /> ENVIROMENTAL HEALTH <br /> FERMIT/SERVICES <br /> Harold Warner <br /> Guntert Sales Div. , Inc. <br /> 222 East Fourth Street <br /> Ripon, California 95366 <br /> Dear Mr. Warner: <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> Enclosed are copies of the test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency. <br /> A tank system is considered tight , according to the current <br /> rules , if the gain is less than . 02 or the loss is less than . 05 <br /> gallons per one hour of testing. If the results are beyond these <br /> parameters , you should consider taking some remedial action. <br /> TANK 11/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> North 10, 000 Diesel +. 005115 Yes <br /> South 4, 000 Gasoline -. 013586 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sine rely , <br /> W. Savage <br /> Certified Tester <br /> 800 162.8378 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />