PANEL SCHEDULE PANEL SCHEDULE NOTES GENERAL NOTES <br /> EXISTING MAIN PANEL "A' TO REMAIN FUNCTIONAL. ALL CIRCUITS TO 11 . EXACT ROUTING OF ALL CONDUITS WITHIN THE EXISTING BUILDING 1 . SHOULD A CONFLICT OCCUR BETWEEN OR WITHIN THE SPECIFICATIONS <br /> VOLTAGE 120,/240LOCATION LUBE BAY REMAIN FUNCTIONAL AS IS UNLESS OTHERWISE NOTED, CONTRACTOR TO SHALL BE DETERMINED BY THE CONTRACTOR. ANY COST REQUIRED AND/OR DRAWINGS, CODES, STANDARDS, REQUIREMENTS, MANUFACTURER'S <br /> PHASE 1 WIRE 3 0 PANEL A (EXISTING) MOUNTING SURFACE VERIFY ALL CIRCUITS AND REMOVE UNUSED CIRCUIT BREAKERS AND TO ROUTE CONDUITS DIFFERENTLY THAN IS SHOWN OF THESE INSTRUCTIONS OR RECOMMENDATIONS, THE MORE STRINGENT AND/OR <br /> BUS AMPS 200A MAIN AMPS 175A DWG. NO. E2 THE ASSOCIATING WIRES. PROVIDE PROPER CIRCUIT INDENTIFICAT10N TAG DRAWINGS SHALL BE INCURRED BY THE E.C.. RESTRICTIVE CONDITION SHALL HAVE PRECEDENCE, AS DETERMINED BY <br /> ON PANEL DOOR. THE CONTRACTING OFFICER. <br /> VOLT AMPS BRKR CKT BUS CKT BRKR VOLT AMPS w DESCRIPTION 12. ALL MATERIALS AND EQUIPMENT SHALL BE DELIVERED TO THE SITE NEW, <br /> DESCRIPTION w 2. THE DRAWINGS REPRESENT THE FINISHED PROJECT UNLESS OTHERWISE <br /> A B AMP P NO. CONN. N0. P AMP A B j MODIFY EXISTING CIRCUIT. PROVIDE AND INSTALL NEW CIRCUIT BREAKER IN THEIR ORIGINAL UNBROKEN PACKAGES BEARING APPROVAL BY U.L., <br /> 30 1 1 3 1 20 EXISTING CKT AS SHOWN. CONTRACTOR TO VERIFY REQUIREMENTS. NEMA, NBFU OR OTHER APPROPRIATE AGENCY, AND INSTALLED PER NOTED, THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION. THE <br /> EXISTING CKT THEIR GUIDELINES. CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK AND HE SHALL <br /> EXISTING CKT 20 1 2 4 1 20 EXISTING CKT PROVIDE AND INSTALL NEW FUEL SUB-PANEL "B" ADJACENT TO EXISTING BE SOLELY RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS, <br /> EXISTING CKT 20 1 5 7 1 20 EXISTING CKT 3 MAIN PANEL "A SEE DWG. "E-2" FOR LOCATION. CONTRACTOR TO 13. CONTRACTOR SHALL PROVIDE A COMPLETE AND FUNCTIONING ELECTRICAL TECHNIQUES, SEQUENCES, <br /> EXISTING CKT 20 1 6 8 1 20 EXISTING CKT FURNISH ALL NEW CIRCUIT BREAKERS AS SHOWN. SYSTEM MEETING THE INTENT OF THESE PLANS AND SPECIFICATIONS. <br /> _ 20 1 9 11 1 20 EXISTING CKT ALL SYSTEMS SHALL BE IN FOR INSPECTION. 3. ALL DIMENSIONS, EXISTING JOB SITE CONDITIONS, AND SERVICE REQUIRE- <br /> EXISTING CKT ® PROVIDE AND INSTALL NEW SWITCH NEUTRAL COMMON TRIP CIRCUIT MENTS SHALL BE VERIFIED BY THE CONTRACTOR BEFORE THE START OF <br /> EXISTING CKT 20 1 10 12 1 20 EXISTING CKT BREAKERS FOR FUEL DISPENSER CIRCUITS PER N.E.C. 514-5, 1993. 14. CONTRACTOR SHALL MAINTAIN GROUND CONTINUITY TO EVERY OUTLET CONSTRUCTION AND/OR FABRICATION OF MATERIALS. IF DISCREPANCIES <br /> EXISTING CKT 20 1 13 - 15 2 EXTERIOR LTS(CKT 1 -12) p PER N.E.C., TABLE 250-95, 1993. ARE ENCOUNTERED, THE ENGINEER SHALL BE NOTIFIED FOR CLARIFICATION. <br /> EXISTING CKT 20 1 14 16 900 SAME AS CKT 14 ABBREVIATIONS 15. ALL WIRES AND CABLES SHALL BE COPPER, 600 VOLT, X12 AWG MINIMUM. 4. CONTRACTOR SHALL COORDINATE WORK BETWEEN ALL TRADES AND <br /> EXISTING CKT 17 19 2 EXISTING CKT EXCEPT CONTROL WIRING WHICH SHALL BE #18 THWN. CONDUCTORS WORKMEN TO CLOSE, PATCH AND REPAIR ALL HOLES WHERE ITEMS ARE <br /> EXISTING CKT 18 20 20 EXISTING CKT A AMPS HPS HIGH PRESSURE SODIUM #10 AWG AND SMALLER SHALL BE SOLID. CONDUCTOR #8 AWG AND REMOVED AND PROVIDED OPENINGS AS NECESSARY FOR NEW WORK. <br /> EXISTING CKT 20 1 21 - 23 EXISTING CKT AFF ABOVE FINISHED FLOOR HTR LARGER SHALL BE STRANDED. TYPE OF INSULATION AS NOTED ON <br /> EXISTING CKT 20 1 22 24 EXISTING CKT AEG ABOVE FINISHED GRADE IG ISOLATED GROUND DRAWINGS AND AS FOLLOWS: 5. ALL WORK SHALL BE DONE IN STRICT ACCORDANCE WITH NATIONAL <br /> FUEL SUB-PNL "B 4640 70 25 27 - - SPACE AWG AMERICAN WIRE GAGE KVA KILOVOLTAMPERS - THHN/THWN INSULATION FOR #4 AWG AND SMALLER. ELECTRICAL CODE (93 EDITION), AND ALL APPLICABLE STATE, COUNTY, <br /> AUX AUXILLARY KW KILOWATT - THW OR THHN/THWN INSULATTION FOR #2 AWG AND LARGER. AND LOCAL CODES APPLYING TO THE PROPOSED CONSTRUCTION. IN THE <br /> 2 SAME AS CKT 25 2000 2 26 28 - - SPACE 2 BAT BATTERY - THW USED FOR ALL PANEL FEEDERS AND SERVICE CONDUCTORS. EVENT OF CONFLICT BETWEEN THE ABOVE AND THESE PLANS AND <br /> SPACE - - 29 31 - - SPACE_ BAD BOARD LCL LONG CONTINUOUS LOAD - THHN INSULATION TYPE SHALL BE USED WHERE CONDUCTORS SPECIFICATIONS, THE MOST RESTRICTIVE SHALL GOVERN. <br /> 20 1 30 32 2 AIR COMPRESSOR BRKR BREAKER LTG LIGHTING ARE INSTALLED IN CONDUITS EXPOSED TO THE WEATHER, <br /> EXISTING CKT — BLDG BUILDING MDP MAIN DISTRIBUTION PANEL 6. CONTRACTOR SHALL VERIFY ALL INFORMATION PERTAINING TO SERVICE <br /> EXISTING CKT 15 1 33 35 20 SAME AS CKT 32 C CONDUIT MECH MECHANICAL 16. ALL ELECTRICAL EQUIPMENT SHALL BE ANCHORED FOR SEISMIC LOADING BY THE UTILITIES AND SHALL INCLUDE THE COST OF ALL WORK BY OR <br /> MH METAL HALIDE RESIST A HORIZONTAL FORCE ACTION IN ANY DIRECTION USING THE FOR THEM IN HIS BID. <br /> EXISTING CKT 20 1 34 36 RONAN CAB CABINET MTD MOUNTED FOLLOWING CRITERIA: <br /> TOTALS - - - - CB CIRCUIT BREAKER NEC NATIONAL ELECTRICAL CODEFIXED EQUIPMENT ON GRADE 33% OF OPERATING WEIGHT 7. ELECTRICAL CONTRACTOR SHALL PROVIDE A COMPLETE AND OPERATIONAL <br /> VOLT AMPS: BUS A - DEMAND FACTOR —x LCL KVA —x 1 .25= - CLG CEILING NL NIGHT LIGHT FIXED EQUIPMENT ON STRUCTURE 50% OF OPERATING WEIGHT ELECTRICAL SYSTEM, EXCEPT THAT THE PROVISIONS FOR OWNER-SUPPLIED <br /> BUS B - DEMAND FACTOR x NON LCL KVA - NTS NOT TO SCALE <br /> CKT CIRCUIT EQUIPMENT SHALL ONLY BE COMPLETED TO THE POINT INDICATED <br /> — _ <br /> TOTAL KVA CO CONDUIT ONLY FOR FLEXIBLY MOUNTED EQUIPMENT USE 2 TIMES THE ABOVE VALUES. ELSEWHERE ON THE DRAWINGS. <br /> - P POLE <br /> TOTAL - COND CONDENSER SIMULTANEOUS VERTICAL FORCE USE 1/3 TIMES HORIZONTAL FORCE. <br /> 19 AMPS - CP CONTROL PANEL RECPT. RECEPTACLE THIS CRITERIA APPLIES TO EQUIPMENT ON THE FLOOR, WALL, OR ROOF 8. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR CONFORMITY TO ALL <br /> CU COPPER ST STAGGERED STRIP LUMINAIRE WITH AN OPERATING WEIGHT OF LESS THAN 1 ,000 LB.. LOCAL CODES AND ORDINACES, THE STATE CALIFORNIA ELECTRICAL <br /> CPU CENTRAL PROCESSING UNIT SAFETY ORDERS, THE NEC AND ANY ADDITIONAL JURISDICTION RELATING <br /> VOLTAGE 120/ 42_Q LOCATION LUBE BAY DS DISCONNECT SWITCH T TRANSFORMER 17. CONTRACTOR IS RESPONSIBLE FOR ALL CORING, CUTTING, PATCHING TO THE WORK. <br /> PANEL B (NEW) MOUNTING SURFACE DWG DRAWING TEL. TELEPHONE AND REFINISHING OF WALLS AND SURFACES WHENEVER IT IS NECESSARY <br /> PHASE 1WIRE 3 TYP TYPICAL PENETRATION. ALL OPENINGS MADE SHALL BE SEALED TO MEET THE 9. ELECTRICAL CONTRACTOR SHALL INCLUDE ALL FEES, INCLUDING <br /> BUS AMPS 100A MAIN AMPS M.L.O. DWG. NO. F2 EMR EMERGENCY <br /> OLT AMPS BRKR CKT BUS CKT BRKR VOLT AMPS v EMT ELECTRICAL METALIC TUBING UL UNDERWRITERS LABORATORY FIRE RATING AND STRUCTURAL INTRGRIIY OF THE PARTICULAR WALL, CONNECTION FEES AND SERVICES CHARGES, AND SHALL FURNISH <br /> jD # <br /> w J DESCRIPTION EF EXHAUST FAN LION UNLESS OTHERWISE NOTED FLOOR, OR CEILING. ALL PERMITS REQUIRED FOR THE ELECTRICAL SYSTEM, <br /> A B AMP P N0. CONN. NO. P AMP A B ES ENERGY SAVING XFMR TRANSFORMER <br /> FUEL ) 1000 20 1 1 2 2 1000 TURBINE (R.U.) EVAP CLR EVAPORATIVE COOLER V VOLTS 18. ALL ELECTRICAL FIXTURE AND EQUIPMENT SHALL BE GROUNDED. ALL 10. IN THE EVENT OF A CONFLICT OR INCOSISTENCY BETWEEN ITEMS <br /> 3 4 20 1000 SAME AS CKT 2 (E), EX, EXISTING CONVENIENCE RECEPTACLES SHALL BE GROUNDING TYPE. INDICATED ON THE PLANS AND/OR SPECIFICATIONS OR WITH CODE <br /> EXIST. WH WATER HEATER REQUIREMENTS, THE NOTES, SPECIFICATIONS OR CODES WHICH <br /> FUEL R) 1000 20 1 5 6 2 1000 TURBINE (S.U.) WP WEATHERPROOF 19. ELECTRICAL CONTRACTOR SHALL FURNISH TEMPORARY CONSTRUCTION ESTABLISH AND PRESCRIBE THE MORE COMPLETE WORK OR THE <br /> 4 7 8 20 1000 SAME AS CKT 6 GFT GROUND FAULT CIRCUIT WTR WATER POWER WHERE REQUIRED. HIGHER STANDARD SHALL PREVAIL. <br /> FUEL 600 20 1 9 10 SPACE INTERRUPTER <br /> 1 12 SPACE G, GND GROUND <br /> 13 14 SPACE LEGEND <br /> 15 16 SPACE <br /> TOTALS 2600 2000 20001 <br /> CIRCUIT BREAKER ® CIRCUIT BREAKER PANELBOARD 277/480V �� FLUORESCENT LIGHT FIXTURE — E — EMERGENCY CIRCUIT/CONDUIT <br /> g <br /> VOLT AMPS: BUS A 4600 DEMAND FACTOR _x LCL KVA —x 1 .25= STRIP LIGHT <br /> BUS B 2000 DEMAND FACTOR 1.0 x NON LCL KVA 6_6 = 6.6 O DOWN LIGHT FIXTURE - VARIATION ® MAIN SERVICE SWITCHBOARD — (E)— EXISTING CIRCUIT/CONDUIT <br /> 6.6 -L STAGGERED STRIP FLUORESCENT <br /> TOTAL 6600 T01FAL KVA — GROUND CONNECTION LUMINAIRE <br /> 10 AMPS 27,0 - - -- - CONDUIT UNDER SLAB OR BELOW GRADE <br /> LP-1 PANEL DESIGNATION, PANEL ' LP-1 ' <br /> WALL MOUNTED DUPLEX GROUNDING RECEPTACLE 1-Q FLUORESCENT FIXTURE, WALL BRACKET —OHE- OVERHEAD ELECTRICAL LINE <br /> NEMA 5-20R AT 18" AFF UON � TELEPHONE OUTLET BOX MOUNTED AT 18' AFF <br /> _ UON WITH (1) 3/4" CONDUIT TO TELEPHONE <br /> QUADRUPLEX (DOUBLE DUPLEX) GROUNDING BOARD/ CABINET (COMBINE TWO OUTLETS PER FO WALL MOUNTED FIXTURE SMOKE DETECTOR <br /> SINGLE LINE DIAGRAM <br /> RECEPTACLE NEMA 5-20R AT 18 AFF LION 3/4"C, THREE PER 1" C.) <br /> WALL PACK FIXTURE ��.®_ FUSED SWITCH <br /> WALL MOUNTED DUPLEX GROUNDING RECEPTACLE DATA OUTLET BOX MOUNTED AT III" AFF LION <br /> W/ GFI NEMA 5-20R AT 18" AFF UON `a WITH (1") 3/4"C. TO CEILING SPACE. zt=� EMERGENCY LIGHT FIXTURE, WALL MOUNTED <br /> t{QTE: ISOLATED GROUND DUPLEX RECEPTACLE �� FLEX CONDUIT MOTOR STARTER <br /> NEMA 5-20R WALL MOUNTED AT 18" AFF EXIT LIGHT FIXTURE, SHADED SECTOR <br /> MAXIMUM DEMAND LOAD DURING LAST � INDICATES FACE, DIRECTIONAL ARROWS � POWER POLE <br /> (EX.) 200A MAIN SERVICE 12 MONTHS = 3,800 KWH, DEC„1994, 1/2" CONDUIT WITH 2 #12 WIRES AS SHOWN. PP <br /> TO REMAIN (120V/24OV, 10,3W) PER PG&E SERVICE PLANNER: 1/2 SWITCHED RECEPTACLE GROUND DUPLEX PB PULLBOX <br /> - - - - - --I- - - - - - - CHARLENE CARNAHAN 0 (209) 942-1461 � If-► HOME-RUN TO PANEL 'A' CIRCUITS 3 AND 5 TOGGLE SWITCH AT + 44" AFF SUBSCRIPTS <br /> F - - t - - I FLUSH MOUNT FLOOR BOX DUPLEX RECEPTACLE A-3,5 INDICATE THE FOLLOWING: 2-TWO POLE, MH MANHOLE <br /> I NEMA 5-20R, GROUNDING TYPE O Q JUNCTION BOX 3-THREE WAY, 4-4WAYS, a,b,c-NUMBER <br /> ^ ^ OF SWITCHES El' FUSIBLE DISCONNECT SWITCH AS NOTED <br /> EXISTINGMETER PG&E A (� FLUSH MOUNT FLOOR BOX QUADRUPLEX �I ❑ FLUORESCENT LIGHT FIXTURE-VARIATIONS <br /> (EX.) F - - 1 1 #A43234 \I RECEPTACLE NEMA 5-20R, GROUNDING TYPE L-1 MANUAL DISCONNECT SWITCH WITH THERMAL , COMBINATION MOTOR STARTER AND DISCONNECT <br /> (( M OVERLOAD PROTECTION. SWITCH WITH HOA SWITCH, NEMA SIZE 1 , AND <br /> C/O 2-POLE 1 I P, I I I FLUSH MOUNT FLOOR BOX TELEPHONE OUTLET � FUSES. <br /> E=_1 C5< TELEPHONE <br /> DISCONNECT SWITCH AS NOTED <br /> © SEVEN DAY TIME CLOCK <br /> I PANEL I I ® FLUSH MOUNT FLOOR BOX DATA OUTLET TELEPHONE BACKBOARD/CABINET 12x4 <br /> FLUSH MOUNT FLOOR BOX ISOLATED GROUND —CT— CABLE TRAY: 12 INCHES WIDE BY 4 INCHES <br /> EXISTING MAIN •A• I I RECEPTACLE NEMA 5-20R FLUORESCENT FIXTURES WITH F1 LIGHT FIXTURE DESIGNATION. DEEP <br /> PANEL "A" TO I I TANDEM WIRING <br /> REMAIN I L - - J i ELECTRICAL PANEL FLUSH MOUNT R <br /> 64 FIXTURE "Ft", 64 WATTS. <br /> L __ - _. - - -I- _ _ J FLUORESCENT FIXTURE WITH CONDUIT COSEALED ABOVE CEILING OR <br /> F LA <br /> - - ELECTRICAL PANEL SURFACE MOUNT EMERGENCY CIRCUIT IN WALL <br /> + CD I <br /> 0 L - -}� CIRCUIT BREAKER PANELBOARD 120/208V REVISIONS <br /> MSS , Pacific General, Irlc• NO. DATE BY COMMENTS SHELL OIL COMPANY <br /> ti Cx ,— ENGINEERING/ARCHITECTURAL SERVICES <br /> 0 EX.) 2' C + FEEDERS TO - HOUSTON TEXAS <br /> o OWER P.O.C.a CO.. C. Lake ET Toro Road Suite 71 7 <br /> REMAIN TEL: <br /> T <br /> n Lake Forest, California 92630 <br /> TEL: (714) 770-2770 FAX: (714) 770-1252 I ! ELECTRICAL PLAN <br /> q� <br /> NEW 100A SUB- R.M.L. ��p yOfMs( �y PLANS PREPARED BY, 2494 FREMONT ST. & FILBERT ST. <br /> 16-CKT PANEL DRAWN BY: U O ���0 FF c�a <br /> 120/24OV, 10, .� E 014840 <br /> 3W PANEL CHECKED BY: A & S ENGINEERING STOCKTON, CALIFORNIA <br /> EXP. 6-30-99 <br /> (FUEL) - - - - EXISTING TO R.M.L. PLANNING ENGINEERING CONSTRUCTION MANAGEMENT SCALE: NONE WIC # 204-7524-1t308 <br /> REMAIN PROJECT NO. k rt 45 QUAIL COURT, SUITE 303 <br /> INDICATES NEW 5AS06 sTa �FCTR�GP°P WALNUT CREEK, CALIFORNIA 94596 DATE: 03-16-95 DRAWING NO. E1 <br /> FII.F N0. T£.OF_,1�.4�F0� PHONE: 510-933-0578 FAX: 510-933-0588 ^,I IFf T nr <br /> — 5AS06EI <br />