Laserfiche WebLink
SAN JOAQLJIN LOCAL. Fim r.TH DISTE22CT <br /> SAMPLING PROTOCIfL FOR ROUTINE TANK REMOVALS <br /> The following represents minimum sampling criterion required for closure compliance. If <br /> contamination is documented during closure, an Unauthorized Release notification must be <br /> filled out and submitted to SJLHD within 5 days. Section 2652, CXR. <br /> WATER NOT PRESENT IN THE TANK PIT <br /> TANK SIZE MINIMUM NUMBER OF LOCATION OF SOIL SAMPLES <br /> SOIL SAMPLES <br /> Less than 1000 llons ONE per tank Fill or pump end of tank <br /> 1000 - 10,000 gallons TWO per tank One at each end of to <br /> 10,001 gallons and up THREE OR MORE Ends and Middle or <br /> per tank generally spaced along <br /> the length of the tank <br /> Piping ONE EVERY 20 LINEAL FEET <br /> WATER IS PRESENT IN TANK PIT <br /> TANK SIZE MINIMUM NO. OF LOCATION OF SOIL MINIMUM NUMBER <br /> SOIL SAMPLES SAMPLES OF WATER SAMPLES <br /> 10,000 GALL40NS From wall next to <br /> OR LESS tank ends at soil/ <br /> (Single Tank) TWO groundwater ONE <br /> interface <br /> GREATER THAN From wall next to ONE <br /> 10,000 GALLONS tank ends at soil/ <br /> OR groundwater <br /> TANK CLUSTER FOUR interface <br /> EH 23 047 12/88 <br />