titITIS Integrity Tank Testing Systems, Inc. 1VJ� <br /> MAY 26 1988 <br /> ENVIRGMENTAL HEALTH <br /> FE M17/SERVICES <br /> TEST DATA AND <br /> TEST RESULTS <br /> January 25 , 1988 <br /> Mr. Yosh Malaga <br /> IIATAGA OLDS-BUICK <br /> 880 South Beckman Road <br /> Lodi, California 95240 <br /> Dear Mr. Mataga: <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> Enclosed are copies c( Lite tee t worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency. <br /> A tank system is considered tight , according to the current <br /> rules , if the gain is less than . 02 or the loss is less than . 05 <br /> gallons per one hour of testlt,g . If th•, results are beyond these <br /> parameters , you should consider taking some remedial action. <br /> TANK fl/ TANK PRO1)TJCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAIIETERS <br /> Service 500 ** Waste Oil -. 01584 Yes <br /> Dept. <br /> **If tank is a 350 gallon capacity , test results would not <br /> change significantly. <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely , <br /> W. Sa age <br /> CertilYied Tester <br /> 800 262-8378 166 Frank West Circle _ Stockton, CA 95206 (209) 466-8036 <br />