Laserfiche WebLink
INVOICE #BB000152 TEST DATE : 09/13/97 <br /> UNDERGROUND TANK TESTERS <br /> 15806 AVENUE 288 <br /> VISALIA, CA 93292 <br /> 209-747-5220 <br /> TANK STATUS REPORT -- ULLAGE TEST <br /> --------------------------------- <br /> ***** CUSTOMER DATA ***** ***** SITE DATA ***** <br /> JOE' S PLACE TRUCK STOP JOE' S PLACE TRUCK STOP <br /> 15600 S . HARLAN RD . 15600 S . HARLAN RD . <br /> LATHROPE, CA. LATHROPE, CA. <br /> 95332 95332 <br /> CONTACT: DHOOT CONTACT: DHOOT <br /> PHONE # : 982-0370 PHONE # : 982-0370 <br /> ***** COMMENT LINES ***** <br /> CURRENT EPA STANDARDS DICTATE <br /> THAT FOR UNDERGROUND FUEL TANKS, THE MAXIMUM ALLOWABLE LEAK/GAIN RATE <br /> OVER THE PERIOD OF ONE HOUR IS . 05 GALLONS . <br /> TANK #1 : DIESEL FUEL 2 TYPE: STEEL SN: - . 07 <br /> TANK IS TIGHT. <br /> TANK #2 : DIESEL FUEL 2 TYPE : STEEL SN: .00 <br /> TANK IS TIGHT. <br /> TANK #3 : REG UNLEADED TYPE: STEEL SN: - . 12 <br /> TANK IS TIGHT. <br /> TANK #4 : DIESEL FUEL 2 TYPE: STEEL SN: . 01 <br /> TANK IS TIGHT. <br /> BOB SMITH <br /> OPERATOR: LIC #91-1431 SIGNATURE : DATE : <br /> -------------------- <br />