Laserfiche WebLink
INVOICE #BG000220 TEST DATE: 09/21/96 <br /> UNDERGROUND TANK TESTERS <br /> 15806 AVENUE 288 <br /> VISALIA, CA 93292 <br /> TANK STATUS REPORT -- ULLAGE TEST <br /> --------------------------------- <br /> ***** CUSTOMER DATA ***** ***** SITE DATA ***** <br /> JOE'S PLACE TRUCK STOP JOE'S PLACE TRUCK STOP <br /> 15600 SO. HARLAN RD. 15600 SO. HARLAN RD. <br /> LATHROP, CA. LATHROP, CA. <br /> 95332 95332 <br /> CONTACT: DHOOT CONTACT: DHOOT <br /> PHONE # : 982-0370 PHONE #: 982-0370 <br /> ***** COMMENT LINES ***** <br /> CURRENT EPA STANDARDS DICTATE <br /> THAT FOR UNDERGROUND FUEL TANKS, THE MAXIMUM ALLOWABLE LEAK/GAIN RATE <br /> OVER THE PERIOD OF ONE HOUR IS . 05 GALLONS . <br /> TANK #1 : DIESEL FUEL 2 TYPE: STEEL SN: . 01 <br /> TANK IS TIGHT. <br /> TANK #2 : DIESEL FUEL 2 TYPE : STEEL SN: - .17 <br /> TANK IS TIGHT. <br /> TANK #3 : REG UNLEADED TYPE: STEEL SN: . 03 <br /> TANK IS TIGHT. <br /> TANK #4 : DIESEL FUEL 2 TYPE: STEEL SN: .12 <br /> TANK IS TIGHT. <br /> OPERATOR: F+ pll SIGNATURE : T ? �/ DATE: <br />