Laserfiche WebLink
INVOICE #YE000244 TEST DATE: 08/13/95 <br /> YARBROUGH ENTERPRISES <br /> 1840 EAST OLIVE AVENUE <br /> PORTERVILLE, CA 93257 <br /> (209) 782-1049 <br /> TANK STATUS REPORT -- ULLAGE TEST <br /> --------------------------------- <br /> ***** CUSTOMER DATA ***** ***** SITE DATA ***** <br /> JOE'S PLACE TRUCK STOP JOE'S PLACE TRUCK STOP <br /> 15600 SOUTH HARLAN ROAD 15600 SOUTH HARLAN ROAD <br /> LATHROP, CA. LATHROP, CA. <br /> 95332 95332 <br /> CONTACT: DHOOT,DALWINDER CONTACT: DHOOT,DALWINDER <br /> PHONE #: 209-982-0370 PHONE # : 209-982-0370 <br /> ***** COMMENT LINES ***** <br /> CURRENT EPA STANDARDS DICTATE <br /> THAT FOR UNDERGROUND FUEL TANKS, THE MAXIMUM ALLOWABLE LEAK/GAIN RATE <br /> OVER THE PERIOD OF ONE HOUR IS . 05 GALLONS. <br /> TANK #1 : DIESEL FUEL 2 TYPE: STEEL SN: . 16 <br /> TANK IS TIGHT. <br /> TANK #2 : REG UNLEADED TYPE: STEEL SN: .02 <br /> TANK IS TIGHT. <br /> TANK #3 : DIESEL FUEL 2 TYPE: STEEL SN: -. 04 <br /> TANK IS TIGHT. <br /> TANK #4 : DIESEL FUEL 2 TYPE: STEEL SN: -. 06 <br /> TANK IS TIGHT. <br /> OPERATOR: SIGNATURE: Q/ ii DATE: <br /> UTTL# 90-1237 <br />