Laserfiche WebLink
PROFESSIfAL <br /> R-M nS CONSULTANTS, INC. SERVICES IN <br /> Architecture <br /> 4118 CORONADO AVENUE, STOCKTON, CA 95204-2313 ElEngineering <br /> Eleecc trical Engineering <br /> PHONE (209) 466.3035 Industrial Engineering <br /> Mechanical Engineering <br /> Pollution Control <br /> Product Design <br /> March 5, 1996 <br /> ._..E .R. Carp-enter. - <br /> 17100 S . Harlan Road _ <br /> P. O . Box 279 <br /> Lathrop, CA 95330 <br /> Attn: Mr. Jay Leslie <br /> Rp : Cathodic Testing of Underground Storage Tank <br /> Dear ,lay: <br /> We performed an inspection of the underground fuel tank at <br /> 17100 S . Harlan Road , Lathrop, on .March 5 , 1996 and report the <br /> following : <br /> Pipe to soil reading: A reading of -1 . 21 volts taken on the <br /> tank indicates the sacrificial anodes are working properly <br /> and that the tank is receiving cathodic protection. <br /> The leak monitoring sensor to the tank was tested and was <br /> working properly. <br /> Based on the above findings the tank and the cathodic system <br /> "are` working=properly" and"require'"no corrective measures -at-this -time . <br /> If you have any questions, please do not hesitate to give us <br /> a call . <br /> I <br /> Sincerely, <br /> R-M-S PROFESSIONAL CONSULTANTS , INC . <br /> Robert M. Snyder, P . E . <br /> RMS/dIs President <br />