INTEGRITY TANK TESTING SERV-tCES <br />P. O. BOX 691736, STOCKTON, CA. 95269 <br />May 10, 1993 <br />San Joaquin County Motor Pool <br />130 North Hunter St. <br />Stockton, Ca. 95201 <br />Dear Mr. Garcia; <br />Following is a summary of the precision testing we recently conducted on your <br />underground storage tanks. <br />Enclosed are copies of the test worksheet, graphs, and/or computer generated <br />summations for your submittal to the appropriate governmental agency. <br />A tank system may be considered tight, according to the current regulations if the test <br />results shown below do not exceed 0.05 gph. If the results are beyond this parameter, <br />an unauthorized release may have occurred, and you should consider taking remedial <br />action. <br /># OR <br />TANK <br />PRODUCTTANK <br />TIGHT <br />PARAMETER <br />LOCATION <br />CAPACITY <br />CONTAINED <br />RESULTS <br />SAN Garage <br />8,000 <br />U/L Gaso <br />-.014 <br />Yes <br />Please advise if you need additional information or service. <br />Sincerely, <br />13X Samage <br />W. N. Savage <br />Certified Tester <br />STOCKTON (209) 474-1375 TOLL FREE (800) 262-8378 <br />