HAZARDOUS AREA NOTES SITE PLAN NOTES
<br /> N.E.C.
<br /> FAA i' I
<br /> TYPICAL N.F.C. ARTICLE 514 CLASS 1 LOCATION (UNDERGROUND TANK -- FILL OPENING) EXISTING PRODUCT DISPENSER TO BE REPROVED. -
<br /> A EXTENT OF CLASS 1, GROUP D, DIVISION 1 LOCATION:
<br /> Any pit, box, or space below grade level, ony part of which is within the Division 1 "
<br /> or 2 classified location. ( 2 NEW MULTI—PRODUCT DISPENSER "MPD. SEE TANK DRAWINGS.
<br /> EXTENT OF CLASS 1, GROUP D, DIVISION 2 LOCATION:
<br /> Up to 18 inches above grade level within a horizontal radius of 10 feet from a loose 3 NEW 3/4" CONDUIT TO NEW "MPD." INSTALL (4) BELDEN 66760
<br /> fill connection and within a horizontal radius of 5 feet from a tight fill connection. CABLE. FOR LEAK DETECTION,
<br /> D TYPICAL N.E.C. ARTICLE 514 CLASS 1 LOCATION (UNDERGROUND TANK — VENT—DISCHARGING UPWARD)
<br /> EXTENT OF CLASS 1, GROUP D, DIVISION 1 LOCATION: NEW 1" CONDUIT TO NEW "MPD." INSTALL POWER WIRES AND
<br /> Within 3 feet of open end of vent, extending in all directions. DATA CABLES PER MANUFACTURER'S SPECIFCIATIONS,
<br /> EXTENT OF CLASS 1, GROUP D, DIVISION 2 LOCATION:
<br /> Space between 3 feet and 5 feet of open end of vent, extending in all directions. "
<br /> NEW 1 CONDUIT TO NEW "MPD." INSTALL (6) #16 TW TWISTED PAIR
<br /> TYPICAL N.E.C. ARTICLE 514 CLASS 1 LOCATION (REMOTE PUMP - OUTDOOR) INDIVIDUALLY SHIELDED CABLES TO SALES COUNTER, FOR INTERCOMS
<br /> EXTENT OF CLASS 1, GROUP D, DIVISION 1 LOCATION: IN DISPENSERS.
<br /> Any pit, box, or space below grade level if any port is within a horizontal distance
<br /> of 10 feet from any edge of pump.
<br /> EXTENT OF CLASS 1, GROUP D. DIVISION 2 LOCATION: 6 NEW 1" CONDUIT WITH PULL. LINE TO PANEL AREA. SPARE FOR FUTURE
<br /> Within 3 feet of any edge of pump, extending in all directions. Also up to 18 inches USE. L? e
<br /> above grade level within 10 feet horizontally from any edge of pump.
<br /> TYPICAL N.E.C. ARTICLE 514 CLASS 1 LOCATION (DISPENSING DEVICE — PITS) ° EXISTING P.I.C. UNITS TO REMAIN. RETAIN EXISTING POWER AND DATA a
<br /> D EXTENT OF CLASS 1, GROUP D, DIVISION 1 LOCATION: WIRING. FIELD VERIFY. REPAIR ANY CIRCUITING DAMAGED DURING
<br /> Any pit, box, or space below grade level, any part of which is within the Division 1 CONSTRUCTION.
<br /> or 2 classified location.
<br /> TYPICAL N.E.C. ARTICLE 514 CLASS 1 LOCATION (DISPENSING DEVICE — DISPENSER) 66D EXISTING STORAGE TANKS TO REMAIN. s
<br /> E EXTENT OF CLASS 1, GROUP D, DIVISION 1 LOCATION:
<br /> Space classification inside the dispenser enclosure is covered in ANSI/UL 87,
<br /> "Power Operated Dispensing Devices for Petroleum Products." NEW 1" CONDUIT WITH (6) BELDEN 66760 CABLES TO TLS-350 PANEL.
<br /> TYPICAL N.E.C. ARTICLE 514 CLASS 1 LOCATION (DISPENSING DEVICE — DISPENSER) 10 NEW 3/4" CONDUIT WITH (6) BELDEN 66760 CABLES,
<br /> F EXTENT OF CLASS 1, GROUP D. DIVISION 2 LOCATION:
<br /> Within 18 inches horizontally in all directions extending to grade from (1) the 11 NEW 3/4" CONDUIT WITH (4) BELDEN 66760 CABLES.
<br /> dispenser enclosure or (2) that portion of the dispenser enclosure containing
<br /> liquid handling com onents. Space classification inside the dispenser enclosure
<br /> is covered in ANSI�UL 87, "Power Operated Dispensing Devices for Petroleum 12 NEW 3/4°' CONDUIT WITH (2) BELDEN 66760 CABLES.
<br /> Products."
<br /> I
<br /> p _ TYPICAL N.E.C. ARTICLE 514 CLASS 1 LOCATION (DISPENSING DEVICE -- OUTDOOR) 13 NEW 3/4" CONDUIT FOR LEAK DETECTION, INSTALL (4) BELDEN 66760
<br /> G
<br /> EXTENT OF CLASS 1, GROUP D. DOASION 2 LOCATION: CABLES. FOR LEAK DETECTION,
<br /> Lip to 18 inches above grade level within 20 feet horizontally of any edge of enclosure.
<br /> 14 NEW 3/4" CONDUIT. INSTALL (3) BELDEN 66760 CABLES.
<br /> NEW 3/4" CONDUIT. INSTALL (2) BELDEN 66760 CABLES.
<br /> 36 --- a --�- -� - " 16 NEW 3/4" CONDUIT. INSTALL (1) BELDEN 66760 CABLE.
<br /> 17 NEW 3/4" CONDUIT WITH (3) #10 PLUS (1) #10 GROUND TO PANEL "F"
<br /> a _ - (VIA 'TURBINE CONTACTORS).
<br /> 16 NEW 3/4" CONDUIT WITH PULL LINE TO PANEL AREA. SPARE FOR
<br /> FUTURE USE.
<br /> 19 NEW 3/4" CONDUIT WITH (4) BELDEN 66760 CABLES TO TLS-350 PANEL.
<br /> 17 > 20 NEW 3/4" CONDUIT WITH (3) BELDEN 66760 CABLES.
<br /> a
<br /> 23 25 21 NEW 3/4" CONDUIT WITH (1) BELDEN 66760 CABLE.
<br /> 13 a „22 NEW OVERFILL ALARM AND ACKNOWLEDGEMENT SWITCH. SEE DETAIL_
<br /> _ _ --- � - - - -- O 5 ON SHEET E2-3.
<br /> CK So _ 2Q 22 34 31 __ _ 34 23 NEW 3/4" CONDUIT WITH (5) #12 PLUS (1) #12 GROUND. CKT F-19.
<br /> 24 I 32 33 24 EXISTING EMERGENCY SHUT--OFF SWITCH TO REMAIN, WIRE PER DIAGRAM
<br /> -�' 10 go® o'?g � 17 3 ON SHEET E2--2.
<br /> U 25 EXISTING COUNTER MOUNTED EMERGENCY SHUT-OFF SWITCH. PROVIDE
<br /> 15 Y $018D [ a _ Q RESET SWITCH AND WIRE SYSTEM PER DIAGRAM ON SHEET E2--2. CL
<br /> 26 NEW TOKHEIM SITE CONTROLLER AND DISTRIBUTION BOX.
<br /> 17 0
<br /> 016 --- 1 I 7 f 39 27 EXISTING RONAN LEAK DETECTION SYSTEM 'TO BE REMOVED AND REPLACED
<br /> �CDa _ --
<br /> 1 ---d- 40 WITH NEW VEEDERROOT TLS--350 SYSTEM. CIRCUIT AS SHOWN.
<br /> CD
<br /> I-- -- __ — - 4 26 NEW PANEL "F.°" SEE SHEET ES1-2.
<br /> 29 EXISTING "ALLIED BOX" S.A.M. AND P.I,C INTERFACE BOX TO REMAIN.
<br /> 0
<br /> 35 (° ALL NEW CONDUITS FROM PANEL AND PUMP CONTROLS TO FUEL ISLANDS
<br /> 42 3OI1 (TYP OF 6) AND FUEL TANKS SHALL_ BE RIGID GALVANIZED STEEL. PVC COATED
<br /> 6 39 7 THROUGHOUT.
<br /> -4------ 2 (TYP OF 4) amnlown
<br /> 40 - 0 ALL CONDUITS FROM FUEL ISLANDS AND FUEL TANKS SHALL BE SEALED
<br /> 0 � � � �� _J31 D EAT AT BOTH ENDS WITH CROUSE HINDS TYPE "EYS" FITTINGS. SEE
<br /> ( n DETAIL A, SHEET E-2.
<br /> 32 ALL ELECTRICAL WORK WI'T'HIN DISPENSERS AND FUEL PUMPS
<br /> UNDERGROUND BELOW CLASS 1 DIVISION 2 LOCATIONS SHALL CONFORM
<br /> TO CLASS 1 DIVISION 1 LOCATION REQUIREMENTS.
<br /> 33 CONTRACTOR TO VERIFY THAT ALL EXISTING WIRING IN HAZARDOUS
<br /> K' ETTLEMAN LANE AREAS MEET HAZARDOUS AREA REQUIREMENTS. UPGRADE IF REQUIRED,
<br /> 34 EXISTING CANOPY LIGHTS, AREA LIGHTS, SIGNS, AND VIDEO CIRCUITING 'TO
<br /> REMAIN. CONTRACTOR TO REPAIR DAMAGED CIRCUITS AS REQUIRED.
<br /> 35 PROVIDE STATIC GROUND PER DETAIL 2, SHEET E-4.
<br /> 36 EXISTING MAIN SERVICE SWITCHBOARD.
<br /> 7 4" CONDUIT WITH PULL LINE TO TLS-350 MONITOR PANEL, STUB
<br /> CONDUIT UP AT VENT RISLR SUPPORT MINIMUM 4" AEI CRA09 E 00 UJ
<br /> AND OAP, FOR FUtURr USE,
<br /> i 36 1" CONDUIT FROM DISPENSER TO DISPENSER WITH (4) #16 TWISTED PAIR
<br /> CABLES ROUTED TO SALES COUNTER, FOR INTERCOMS IN DISPENSERS.
<br /> Ln
<br /> 39 1" CONDUIT FROM DISPENSER TO DISPENSER WITH (2) #16 TWISTED PAIR
<br /> CABLES ROUTED TO SALES COUNTER, FOR INTERCOMS IN DISPENSERS.
<br /> 4O 1" CONDUIT FROM DISPENSER TO DISPENSER. SPARE FOR FUTURE USE.
<br /> 4 3/4" CONDUIT FROM DISPENSER -TO DISPENSER, WITH (2) BELDEN
<br /> #66760 CABLES, FOR LEAK DETECTION.
<br /> C4 D 3/4" CONDUIT FROM DISPENSER TO DISPENSER, WITH (1) BELDEN owns
<br /> #66760 CABLE. FOR LEAK DETECTION,
<br /> 43 NEW "POWER SOLUTIONS" DISPENSER MANAGER. SEF SHEETS E2-2
<br /> AND E2--5,
<br /> �C YJ 0ROUP INC
<br /> ARCHITECTURE-ENGINEERING-
<br /> -ENMONMENTAL SERVICES
<br /> 1201 S. BEACH BLVD. STE. 207
<br /> LA HABRA, CA 90631
<br /> (562) 9026023
<br /> JOHN W. JOHNSON, ARCHITECT
<br /> w
<br /> consultant job#
<br /> 5314.10
<br /> master release date
<br /> O. PP WEST COAST PRODUCTS RASTER REVISIONS exeprojectto drawemaster
<br /> � � drag drawn by
<br /> NO. DATE REVISIONS RX PROJECT RELEASENORTH
<br /> a 1 8/26/02 REVISED PER DID ADDENDUM #1 � � CAM _
<br /> PERMIT FilenameFACO2076D1 1
<br /> Facility/Project
<br /> t 0 20 40 60 BID
<br /> 02076
<br /> CONST® sl�e eFn m
<br /> _._.__.._
<br /> (
<br /> IN FEET )
<br /> 1 inch =20 ft. _ ____ __ _� - _--_-�- AS-BUILT
<br />
|