Laserfiche WebLink
9. FILL RISER CONTAINMENT SUMP TESTING <br /> •Facility is Not Equipped With Fill Riser Containment Sumps ❑ <br /> Fill Riser Containment Sumps are Present,but were Not Tested ❑ <br /> Test Method Developed By: ❑ Sump Manufacturer M Industry Standard ❑Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure ❑Vacuum M Hydrostatic <br /> ❑ Other(Spec) <br /> Test Equipment Used: Incon Sump Tester Equipment Resolution: +/-0.002" <br /> Fill Sump#87-2 Fill Sump#87-1 Fill Sump#87-3 Fill Sump#91 <br /> Sump Diameter: <br /> 42 42„ 42„ 42„ <br /> Sump Depth: 50 <br /> 48>, 48„ 48" <br /> Height from Tank Top to Top of N/A N/A N/A N/A <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 21" 19" 18" 18" <br /> Electrical Penetration: <br /> Condition of sump prior to Good Good Good Good <br /> testing: <br /> Portion of Sump Tested 2"above piping 2"above piping 2"above piping 2"above piping <br /> Sump Material: Fiberglass Fiberglass Fiberglass Fiberglass <br /> Wait time between applying <br /> pressure/vacuum/water and 30 minutes 30 minutes 30 minutes 30 minutes <br /> starting test: <br /> Test Start Time: 10:34am 10.51am 10.34am 10.5lam 10:34am 10:51am 10:34am 10:51am <br /> Initial Reading(Rj): 0.7896 0.7899 4.4916 4.4890 3.7672 3.7659 4.3772 4.3745 <br /> Test End Time: 10:50am 11:07am 10:50am 11:07am 10:50am 11:07am 10:49am 11:06am <br /> Final Reading(RF): 0.7900 0.7893 4.4904 4.4887 3.7659 3.7655 4.3757 4.3732 <br /> Test Duration: 16 min. 16 min. 16 min. 16 min. 16 min. 16 min. 1- min. 1- min. <br /> Change in Reading(RF-R,): +.0004 -.0006 -.0012 -.0003 -.0013 -.0004 -.0015 -.0013 <br /> Pass/Fail Threshold or Criteria: +/-0.002" +/-0.002" +/-0.002" +/-0.002" <br /> Test Result: X Pass ❑Fail X Pass ❑Fail X Pass ❑Fail X Pass ❑Fail <br /> Is there a sensor in the sump? M Yes ❑No M Yes ❑No M Yes ❑No M Yes ❑No <br /> Does the sensor alarm when <br /> either product or water is El Yes ❑No M NA El Yes❑No ENA El Yes El No ENA ❑ Yes ❑No ENA <br /> detected? <br /> Was sensor removed for testing? ® Yes ❑No ❑NA M Yes ❑No DNA M Yes❑No DNA M Yes ❑No DNA <br /> Was sensor properly replaced and M yes ❑No ❑NA M Yes ❑No DNA M Yes ❑No DNA M Yes ❑No DNA <br /> verified functional after testing? <br /> Comments- (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> "Sensor functionality was not confirmed This procedure is not part of the <br /> Secondary Containment testing scope of work". <br />