Line Leak Detector Test Data Sheet <br /> Station # Arco SS 2076 Date 12/15 2016 <br /> Address 800 E. Kettleman Lane, Lodi, CA <br /> Test Information <br /> 2 3 4 5 <br /> Product 87 91 <br /> Manufacturer VR VR <br /> Model 848480 848480 <br /> Full Operating Pressure (psi) 38 36 <br /> Line Bleed Back(ml) NA NA <br /> Trip Time (sec) NA NA <br /> Metering Pressure (psi) NA NA <br /> F/E Holding Pressure (psi) 28 34 <br /> Test Leak Rate (ml/min)(gph) 189ml 189m1 <br /> PASS or FAIL P P <br /> Comments: <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct. The mechanical leak test detector test pass/fail is determined using a low <br /> flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor Gettler-Ryan Inc. <br /> Technician David Rouse Lic# <br /> Signature <br />