Laserfiche WebLink
Htut-,W Mj <br /> SAN J 0 A Q I j <br /> IN <br /> EnvironWe t;H JI'Department <br /> COUNT(�YJ— <br /> ENVIRONMENTALHEALTH <br /> t-�rn�^TRR��IT <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> ARCO 07049 300 E Kettleman Ln, Lodi December 15, 2017 <br /> UST System Observations <br /> 319 CCR 2635(b) No spill bucket,failed to contain five gallons,or failed to provide a means to keep it empty o V ❑R ❑COS <br /> 320 CCR 2635(b)(2) Overfill prevention system not present or failed to meet overfill requirements o V o R o COS <br /> 321 CCR 2635(b)(2) Overfill prevention was overridden o V o R c COS <br /> 322 HSC 25281.6(a) Unburied below grade emergency generator system failed to meet exemption status a V ❑R o COS <br /> 323 HSC 25283,5(a) Unburied below grade UST system failed to meet exemption status a V a R o COS <br /> 324 CCR 2717.1(g) Tampered with red tag a V ❑R ❑COS <br /> 325 CCR 2717,1(0 Deposited petroleum into a red tagged UST a V o R ❑COS <br /> 326 HSC 25299(a)(9) Tampered with or disabled leak detection devices or alarms a V ❑R ❑COS <br /> 327 CCR 2631.1 UST system not compatible with the substance stored a V n R a COS <br /> 328 HSC 25298 Failed to comply with temporary closure requirements a V o R o COS <br /> 329 HSC 25298 Failed to comply with all permanent closure requirements ❑V ❑R a COS <br /> 330 CCR 26360(6) Failure to meet all requirements in lieu of a line leak detector for emergency generator tank system a V o R o COS <br /> 331 CCR 2630(d) Secondarily contained piping not maintained to allow liquid to drain into sump a V u R ❑COS <br /> 332 CCR 2631(b),2631(d) Primary and/or secondary containment not constructed in accordance with the established standards ra V a R o COS <br /> Single-Walled Non-Pressurized Piping <br /> 401 CCR 2636(a)(3) Suction piping not properly sloped or incorrectly located check valve n V o R a COS <br /> 402 CCR 2643(d) Daily monitoring of suction pipe(pre-Jan 1984)not performed a V ❑R o COS <br /> 403 CCR 2643(d) Triennial 0.1 gph line test for conventional suction piping not performed(pre-January 1984) iiV a R o COS <br /> 404 CCR 2643(e) Biennial 0.1 gph test for gravity piping not performed(pre-January 1984) e,V o R a COS <br /> Other Violations <br /> 2010 See below Unlisted General violation a V o R o COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 5 HSC 25291(e)Water in secondary containment not removed, analyzed, and properly disposed of(pre-Jul 2003). <br /> Liquid was observed in the premium submersible turbine pump(STP) sump and the 87 slave fill sump. If water <br /> could enter into the secondary containment by precipitation or infiltration, it must be removed and disposed of <br /> properly. The service technician removed about 112 cup of liquid from the premium STP sump and the 87 slave fill <br /> sump. Ensure that all sumps and annular spaces are maintained free of liquid. <br /> This was corrected on site. <br /> This is a repeat violation, Class II. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by January 14, 2018. <br /> FA0003633 PR0231349 SCO01 12/15/2017 <br /> EHD 23-01 Rev.10/31/2017 Page 3 of 4 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.$)cehd.com <br />