Laserfiche WebLink
!, Integrity Tank Testing Syste s, Inc. <br /> -."A awl TS <br /> TEST DATA AND <br /> TEST RESULTS <br /> March 24 , 1988 <br /> Mr. 0. J. Stevens <br /> COMMERCIAL TRANSPORT <br /> 10250 Linne Road <br /> Tracy , California 95376 <br /> Dear Mr. Stevens : <br /> Following is a summary of the ,precision testing we recently <br /> conducted on your underground ptorage tank(s ) . <br /> Enclosed are copies of the test worksheets and graphs gene— <br /> rated for your submittal to the appropriate governmental agency. <br /> A tank system is considered tight , according to the current <br /> rules , if the gain is less than . 02 or the loss is less than . 05 <br /> gallons per one hour of testing. If the results are beyond these <br /> parameters , you should consider taking some remedial action . <br /> T..NK #/ TANK PRODUCT 'TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> N/W of 10 , 000 Diesel Fuel —. 039814 Yes <br /> office <br /> 'lease contact us if you need additional assistance or <br /> information. <br /> Sincerely , <br /> W. Savage <br /> Certified `rester <br /> 800 262-8378 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />