Laserfiche WebLink
ITTSIntegrity Tank Testing Systems, Inc. <br /> RECEIVED <br /> JAN 2 5 1988 <br /> y� jV Q <br /> FLEET oNGS&LOAN TEST DATA AND <br /> F. <br /> AMERICAN SAVINGS <br /> TEST RESULTS <br /> FLEET ap�Rp,�iaNS J an u a ry 5 , 1988 <br /> Aµ�1�SA'4 1G5 a ori► <br /> Mr. Richard Robbins <br /> AMERICAN SAVINGS & LOAN <br /> Fleet Operations , P. 0. Drawer D <br /> Stockton, California 95201 <br /> Site : 1888 Lockheed Court, Stockton, CA <br /> Dear Mr. Robbins : <br /> Pc�;l,ls�win <br /> is, a sttir.mar7 of the precision testing we recentAy <br /> OLD your uudP_rgt,:'ui1U otorage tank(s). <br /> E,iclased are copies u-; the test worksheets and graphs gene- <br /> s f,ir yn+ir submittal to the appropriate governmental agency. <br /> A tank system is consiriered tight . according to the current <br /> i,`' „a gain is Less than . 02 or the loss Ls less than . 05 <br /> �-cellon.:, v•er one hour of testing. If the results are bevond these <br /> parameters , you should consider taking some remedial action. <br /> 'J"AN"K iii TANK PRODUCT TEST WITHIN TICILT <br /> LOGATIO`7 CAPACITY CONTAINED RESULTS TANK PARAMi:".r`H S <br /> - N/E office 12 , 000 U/L Gas - , 03728 Yes <br /> { (north) <br /> N/E office 12 , 140 U/L Gas -. 0367 Yes <br /> (south) <br /> South of 10 . 000 Prem, U/L Gas -. 0394 Yes <br /> / blain Bldg. <br /> Pleas, c(,j; ,, ,.ci_ us .i! .'',.C--'ed addf:.ional C'ssistance or <br /> .i_nf0rmatsinccrcly3 <br /> f <br /> W. Savage <br /> 800 262 TEST 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />