Laserfiche WebLink
{ a a IatogdtT Twat Testtap$Tste..as, Jmasp� 4 `7"i <br /> DEC 19 7988 <br /> TEST DATA AND <br /> "°RI 11 SA;r3"q' LOAM EST RESULTS <br /> December 19 , 1988 <br /> American Savings $ Loan <br /> P . 0 . Drawer D <br /> Stockton, California <br /> Mr . Richard Robbins : <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank (s) . <br /> Enclosed are copies of the test worksheets and computer <br /> generated data for your submittal to the appropriate governmental <br /> agency . <br /> A tank system is considered tight , according to the current <br /> rules , if the loss or gain is less than . 05 gallons per one hour <br /> of testing . If the results are beyond these parameters , you <br /> should consider taking some remedial action . <br /> TANK #/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY C014TAINEO RESULTS TANK PARAMETERS <br /> N/E Of Off. <br /> Middle Tnk 12 , 000 U/L Gaso . - . 036 Yes <br /> S/ E Of Off . <br /> South Tnk 10, 000 U/L Gaso . - . 018 Yes <br /> S/W of Off 10, 000 U/L Gaso . - . 053 No <br /> Please contact us if you need additional assistance or <br /> information . <br /> Sincerely , <br /> A��"00 0-Z' <br /> W. N . Savage <br /> Certified Tester <br /> 800 262.8378 166,Fzcmk West Qm4g $t9(wQ4C �$� " y :' ��a••t' <br />